EDSX5-92H Datasheet, PDF (1/8 Pages) Fuji Electric – PRESSURE TRANSMITTER | |||
|
PRESSURE TRANSMITTER
DATA SHEET
FKG...5
The FCX â AIII pressure transmitter accurately measures
gauge pressure and transmits a proportional 4 to 20mA
signal.
The transmitter utilizes a unique micromachined capacitance
silicon sensor with state-of-the-art microprocessor technol-
ogy to provide exceptional performance and functionality.
FEATURES
1. High accuracy up to ±0.04%
0.065% accuracy as standard, 0.04% accuracy as option.
Fujiâs micro-capacitance silicon sensor assures this ac-
curacy for all elevated or suppressed calibration ranges
without additional adjustment.
2. Minimum environmental inï¬uence
The âAdvance Floating Cellâ design which protects the
pressure sensor against changes in temperature, and
overpressure substantially reduces total measurement
error in actual ï¬eld applications.
3. Fuji/HART® bilingual communications protocol
FCXâAIII series transmitter offers bilingual communica-
tions to speak both Fuji proprietary protocol and HART®.
Any HART® compatible devices can communicate with
FCXâAIII.
4. Application ï¬exibility
Various options that render the FCXâAIII suitable for al-
most any process applications include:
â Full range of hazardous area approvals
â Built-in RFI ï¬lter and lightning arrester
â 5-digit LCD meter with engineering unit
â Stainless steel electronics housing
5. Burnout current ï¬exibility (Under Scale: 3.2 to 4.0mA,
Over Scale: 20.0 to 22.5mA)
Burnout signal level is adjustable using Model FXW
Hand Held Communicator (HHC) to comply with NAMUR
NE43.
6. Dry calibration without reference pressure
Thanks to the best combination of unique construction
of mechanical parts (Sensor unit) and high performance
electronics circuit (Electronics unit), reliability of dry
calibration without reference pressure is at equal level as
wet calibration.
SPECIFICATIONS
Functional speciï¬cations
Service:
Output signal:
Power supply:
Liquid, gas, or vapour
4 to 20mA DC with digital signal super-
imposed on the 4 to 20mA signal.
Transmitter operates on 10.5V to 45V DC
at transmitter terminals.
10.5V to 32V DC for the units with optional
arrester.
[ L-Type ]
[ T-Type ]
Span, range and overrange limit:
Type
Span limit [kPa] {bar}
Range limit
[kPa] {bar}
Overrange
limit
Min.
Max. Lower limit Upper limit [MPa] {bar}
F KG 01
FKG 02
FKG 03
FKG 04
FKG 05
1.3
{0.013}
5
{0.05}
30
{0.3}
100
{1}
500
{5}
130
{1.3}
500
{5}
3000
{30}
10000
{100}
50000
{500}
â100
{â1}
â100
{â1}
â100
{â1}
â100
{â1}
â100
{â1}
130
{1.3}
500
{5}
3000
{30}
10000
{100}
50000
{500}
1
{10}
1.5
{15}
9
{90}
15
{150}
75
{750}
Remark: To minimize environmental inï¬uence, span should be greater
than 1/40 of the max. span in most applications.
â Lower range limit (vacuum limit) ;
Silicone ï¬ll sensor: See Fig. 1
Fluorinated ï¬ll sensor: 66kPa abs (500mmHg abs) at
below 60°C
â Conversion factors to different units;
1 MPa=103 kPa=10bar=10.19716kgf/cm2= 145.0377psi
1kPa=10mbar=101.9716mmH2O =4.01463inH2O
Load limitations: see ï¬gure below
[Ω]
2000
1474Ω
1500
R=
E-10.5
(Imax+0.9)x10-3
1000
500
250
577Ω
Operating
area
24V
45V
0
10 16.35
50 E[ V ]
10.5V
Power voltage (DC)
Note: For communication with HHC(1) (Model: FXW), min. of 250 ïï
required.
EDSX5-92h