EDSX5-87A Datasheet, PDF (1/8 Pages) Fuji Electric – FCX – C2 PRESSURE TRANSMITTER
FCX – C2 PRESSURE TRANSMITTER
DATA SHEET
FKP...4
The FCX –C2 pressure transmitter accurately measures
gauge pressure and transmits proportional 4 to 20mA sig-
nal.
The transmitter utilizes the unique micromachined capaci-
tive silicon sensor with state-of-the-art microprocessor tech-
nology to provide exceptional performance and functionality.
FEATURES
1. High accuracy ±0.1%
0.1% accuracy is a standard feature. Fuji’s micro-capaci-
tance silicon sensor assures this accuracy for all elevated
or suppressed calibration ranges without additional ad-
justment.
2. Minimum environmental influence
The “Advance Floating Cell” design which protects the
pressure sensor against changes in temperature, and
overpressure substantially reduces total measurement
error in actual field applications.
3. Fuji/HART® bilingual communications protocol and
FOUNDATION™ fieldbus and Profibus™ compatibility
FCX–C2 series transmitter offers bilingual communica-
tions to speak both Fuji proprietary protocol and HART®.
Any HART® compatible devices can communicate with
FCX–C2. Further, by upgrading electronics FOUNDA-
TION™ fieldbus and Profibus™ are also available.
4. Application flexibility
Various options that render the FCX – C2 suitable for al-
most any process applications include:
– Analog indicator at either the electronics side or ter-
minal side
– Full range of hazardous area approvals
– Built-in RFI filter and lightning arrester
– 5-digit LCD meter with engineering unit
5. Burnout current flexibility (Under Scale: 3.2 to 3.8mA,
Over Scale: 20.8 to 21.6mA)
Burnout signal level is adjustable using Model FXW Hand
Held Communicator (HHC) to comply with NAMUR NE43.
6. Dry calibration without reference pressure
Thanks to the best combination of unique construction
of mechanical parts (Sensor unit) and high performance
electronics circuit (Electronics unit), reliability of dry
calibration without reference pressure is at equal level
as wet calibration.
SPECIFICATIONS
Functional specifications
Service:
Liquid, gas, or vapour
Span, range and overrange limit:
Type
Span limit [kPa] {bar}
Min.
Max.
Range limit
[kPa] {bar}
Overrange
limit
[MPa] {bar}
FKP˘01
FKP˘02
FKP˘03
FKP˘04
8.125
{0.08125}
31.25
{0.3125}
187.5
{1.875}
625
{6.25}
130
{1.3}
500
{5}
3000
{30}
10000
{100}
–100 to +130
{–1 to +1.3}
–100 to +500
{–1 to +5}
–100 to +3000
{–1 to +30}
–100 to +10000
{–1 to + 100}
1
{10}
1.5
{15}
9
{90}
15
{150}
— Lower range limit (vacuum limit) is;
Silicone fill sensor: See Fig. 1
Fluorinated fill sensor: 66kPa abs (500mmHg abs) at
below 80°C
— Conversion factors to different units;
1 MPa=103 KPa=10bar=10.19716kgf/cm2= 145.0377psi
1KPa=10mbar=101.9716mmH2O =4.01463inH2O
Output signal: 4 to 20mA DC with digital signal super-
imposed on the 4 to 20mA signal.
EDSX5-87a
Date Jun. 1, 2006