EDSX5-77 Datasheet, PDF (1/8 Pages) Fuji Electric – FCX –AX SERIES PRESSURE TRANSMITTER Hydroseal® Diaphragm Version
FCX –AX SERIES PRESSURE TRANSMITTER
Hydroseal® Diaphragm Version
DATA SHEET
FHG,FKG...3
FEATURES
1. Unique hydroseal diaphragm
Permeation of hydrogen into the detecting unit through
seal diaphragm can be suppressed thanks to the unique
seal diaphragm (double coating) which employs coating
of gold and ceramic.
Micro Capacitance
Silicone sensor
Process
cover
Base material
(SUS316L)
Ceramics
coating
Sensor
unit
Sealing diaphragm
coated with gold
and ceramics
Gold
coating
2. High accuracy
± 0.15% accuracy for all calibrated spans is the standard
feature for pressure transmitter covering 50 to 10000kPa
(or 0.5 to 100 kgf/cm2). Fuji's Micro-capacitance silicon
sensor assures this feature.
3. Minimum environment influence
Fuji's patented "Advanced Floating Cell" design which
protects the pressure sensor against changes in tempera-
ture and overpressure substantially reduces total meas-
urement error in actual field applications.
4. Replaceable Communication Module
Fuji micro-electronics manufacturing technology offers
replaceable communication module that makes FCX–AX
transmitter very unique in design. In case of change in
communication protocol, all that needs to be done is just
to replace the module and the transmitter gets upgraded
to the new version.
5. Fuji/HART bilingual communication module
The communication module is "bilingual" to speak both
Fuji proprietary protocol and HART. Any HART compatible
devices can communicate with FCX–AX series trans-
mitters.
6. Application flexibility
Various options that render the FCX–AX series suitable
for almost any process applications include.
— Analog indicator at either the electronics side or ter-
minal side
— Full range of hazardous location approvals
—
4
1
2
-digit
LCD
meter
— Stainless steel electronics housing
— Built-in RFI filter and lightning arrester
7. Burnout current flexibility (Under Scale: 3.2 to 3.8mA,
Over Scale: 20.8 to 21.6mA)
Burnout signal level is adjustable using Model FXW hand
Held Communicator (HHC) to comply with NAMUR NE43.
(Available for amplifier unit from version 24 and FXW (HHC) version
5.3.)
8. Dry calibration without reference pressure
Thanks to the best combination of unique construction
of mechanical parts (Sensor unit) and high performance
electronics circuit (Electronics unit), reliability of dry
calibration without reference pressure is at equal level
as wet calibration.
SPECIFICATIONS
Functional specifications
Type:
Model FHG: 4 to 20mA, Traditional type
Model FKG: 4 to 20mA with digital signal, Smart type
Service:
Liquid, gas, or vapour
Span, range and overrange limit:
Type
Static
pressure
[MPa]
(kgf/cm2)
Span limit
[kPa] (kgf/cm2)
Min. Max.
FHG/ FHG/
FKG FKG
Range limit
[kPa] (kgf/cm2)
Lower Upper
limit
limit
F G 02
F G 03
F G 04
–0.1 to 0.5
(–1 to 5)
–0.1 to 3
(–1 to 30)
–0.1 to 10
(–1 to 100)
50
(0.5)
300
(3)
1000
(10)
500
(5)
3000
(30)
10000
(100)
Permis- 500
sible
(5)
negative
pressure
limit
3000
(30)
10000
(100)
Over
range
lemit
[MPa]
(kgf/cm2)
1.5
(15)
9
(90)
15
(150)
— Lower range limit (vacuum limit) ;
Silicone fill sensor: See Fig. 1
Fluorinated fill sensor: 66kPa abs (500mmHg abs) at
below 60°C
— Conversion factors to different units;
1 MPa=103 kPa=10bar=10.19716kgf/cm2= 145.0377psi
1kPa=10mbar=101.9716mmH2O =4.01463inH2O
Output signal:
Model FHG: 4 to 20mA DC 2-wire
Model FKG: 4 to 20mA DC with digital signal super-
imposed on the 4 to 20mA signal.
EDSX5-56-27b7
Date Mar. 10, 1999