English
Language : 

EDS9-24A Datasheet, PDF (1/4 Pages) Fuji Electric – FC SERIES PT TYPE DISTRIBUTOR (48mm width)
FC SERIES PT TYPE DISTRIBUTOR (48mm width)
DATA SHEET
PTL
The FC series PT type distributor converts a current signal
(4 to 20mA DC) from the transmitter into a voltage signal (1
to 5V DC ) then distributes the voltage signal to each re-
ceiver. In addition, the distributor is provided with built-in
transmitter power supply.
Its structure is plug-in style.
SPECIFICATIONS
INPUT SPECIFICATION
Input signal:
1 point
Input type
Input signal
Input resistance
Current
4 to 20mA DC
250Ω
OUTPUT SPECIFICATION
Output signal: 2 points
Output type
Voltage
Output signal
1 to 5 V DC
Allowable load re- 500kΩ or over (reception,
sistance
non-insulation) 15kΩ or over
(with output buffer)
POWER SUPPLY
Power supply: 24V DC (20 to 30V DC)
24V AC, +13%, –10%,(47 to 63Hz)
100V AC (85 to 132V AC / 47 to 63Hz)
200V AC (187 to 264V AC / 47 to 63Hz)
as specified.
Power consumption:
Approx. 2W (at DC power)
Approx. 6VA (at AC power)
OPERATION CONDITION
Ambient temperature:
0 to 50°C
Ambient humidity:
Less than 90%RH (no condensation)
Outline dimension (HxWxD):
96 x 52 x130mm
Mass:
Appox. 300g
Housing:
Plastic housing (color: black)
Mounting method:
Panel mounting or DIN rail mounting
CHARACTERISTICS
Accuracy:
Less than ± 0.1% of full span
Response time: Less than 0.1 sec. (90% response)
Dielectric strengh: 1500V AC, 1 min. (indicated below)
Insolation resistance:
500V DC, 100MΩ or over (indicated be-
low)
Reception only: Input/Output - Ground
Non-insulation type:
Input/Output•Power - Ground
Non-insulation with buffer:
Input/Output•Power - Ground
Power insulation with buffer:
Input/Output - Power - Ground
Power I/O insulation with buffer:
Input - Output - Power - Ground
Ambient temperature effect:
Less than ± 0.15% of full span/10°C
Power regulation effect:
Less than ± 0.1% of full span
CODE SYMBOLS
1 2345678
PLT2V 1
2
V
A0
B1
C1
D1
E1
D2
E2
D3
E3
Description
Input signal
4 to 20mA DC
Output signal
1 to 5V DC
Output system
Reception only
Non-insulation type
Non-insulation with buffer
Power insulation with
buffer
Power I/O insulation with
buffer
Power insulation with
buffer
Power I/O insulation with
buffer
Power insulation with
buffer
Power I/O insulation with
buffer
Power supply
None
24V DC
24V DC
24V DC/ 24V AC (50/
60Hz)
24V DC/24V AC (50/
60Hz)
100V AC (50/60Hz)
100V AC (50/60Hz)
200V AC (50/60Hz)
200 V AC (50/60Hz)
EDS9-24a
Date Feb. 20, 1996