EDS8-10E Datasheet, PDF (1/4 Pages) Fuji Electric – 2-WIRE UNIVERSAL TEMPERATURE TRANSMITTER | |||
|
Field-mounted Two-wire Signal Conditioners
2-WIRE UNIVERSAL TEMPERATURE TRANSMITTER
(HART® communication, intrinsically safe/explosion-proof)
MODEL
FRC
MODEL & SUFFIX CODE SELECTION
MODEL
ENCLOSURE
0 : None *1
1 : Diecast aluminium
2 : Stainless steel casting
SAFETY APPROVAL
A : None
C : CENELEC flameproof (ATEX)
E : CENELEC intrinsically safe (ATEX)
LCD DISPLAY
0 : Without
1 : With
WIRING CONDUIT *2
0 : None
1 : 1/2 NPT
2 : M20 Ã 1.5
3 : PG 13.5
FRCââââA
*1. Choose the suffix code 0 for âWiring Conduitâ
*2. Confirm selectable combinations of approval and wiring con-
duit types in the table below.
Functions & Features
⢠Universal input: mV, V, T/C and RTD
⢠High accuracy
⢠HART communication
⢠Intrinsically safe and explosion-proof approval
⢠CE marking (conforms to ATEX and EMC)
⢠Optional stainless steel enclosure
⢠Programming via hand-held communicator or via PC
⢠A wide variety of T/C and RTD types
⢠Self diagnostics
⢠Input-output isolated
â SELECTABLE WIRING CONDUITS SPECIFIC TO EACH APPROVAL
âNâ marked combinations are not selectable.
APPROVAL
CONDUIT
A
C
E
0
Y
N
Y
1
Y
Y
Y
2
Y
Y
Y
3
Y
N
Y
RELATED PRODUCTS
⢠PC Configurator Software
⢠HART modem*
MACTek VIATOR RS232 HART® IF recommended
⢠Hand-held communicator*
* Consult HART® Communication Foundation (HCF) web site :
www.hartcomm.org
GENERAL SPECIFICATIONS
Degree of protection : NEMA 4X, IP65
Wiring conduit : See âModel & Suffix Codeâ.
Electrical connection : M3.5 screw terminals (torque 0.8 N·m)
Materials
Transmitter housing : Flame-resistant resin (black)
Screw terminals : Nickel-plated brass
Enclosure :
Diecast aluminium standard (polyurethane coated)
or stainless steel casting (equivalent to type 316,
epoxy resin coated).
Enclosure color :
Body : Silver
Cover : Blue (equivalent to Munsell GPB3.5/10.5)
Silver for stainless steel
Mounting bracket assembly :
Stainless steel 304
Applicable pipe :
1â 1/2 min.; 2â max.
Isolation :
Input to output to outdoor enclosure
User-configurable parameters :
· Input sensor type
· Number of wires (RTD)
· Input range
· Output range (via HART® only)
· Output calibration
· HART communication mode
· HART network mode
Burnout (T/C & RTD) :
Upscale, downscale or no burnout selectable
(standard: upscale);
Also detects wire breakdown and overrange input
exceeding the electrical design limit for DC input.
Cold junction compensation (T/C) :
CJC sensor incorporated
Damping time :
0 to 30 sec. (standard : 0)
Fuji Electric France S.A.S.
EDS8-10e
DATE October 2009
|
▷ |