EDS3-104C Datasheet, PDF (1/4 Pages) Fuji Electric – INFRARED CO2 CONTROLLER
INFRARED CO2 CONTROLLER
DATA SHEET
ZFP9
This is a non-dispersion type infrared CO2 gas analyzer. It
accurately measures the concentration of CO gas in the air,
2
indicates the result and simultaneously outputs an analog
signal. Since upper and lower limit alarm functions are stand-
ard it can also be used as a controller.
This instrument is suitable for use as a CO meter in green
2
houses, building ventilation systems, CA (Controlled Atmos-
phere) storage facilities, and so on.
FEATURES
1. Use of high-performance infrared-ray system
2. Excellent stability and easy maintenance
3. Control with upper/lower limit alarm functions possible
4. Compact and lightweight (Approx. 3kg)
SPECIFICATIONS
Functional specifications
Measuring system:
NDIR (non-dispersion infrared ray system)
Measured gas: CO2 in the air
Measuring range: 0 to 0.2%, 0 to 0.3%, 0 to 1%, 0 to 5%,
0 to 10%, 0 to 20% CO2 (as specified)
Output signal: 4 to 20mA DC nonlinear (max. load re-
sistance 350Ω)
or 0 to 100mV DC nonlinear (output re-
sistance 100Ω)
Note) Linear ouput is available only for 0 to 0.2%
range, 4 to 20mA DC or 0 to 100 mV DC.
Alarm function: Alarm setting range; 0 to 100% FS
Setting method; set value display on
indicator with internal upper/lower
limit setting VR's
Output; relay contact (2 x 1c), 250V AC,
3A (resistive load)
Alarm hysteresis width; ± 4% of scale
length (at 50% FS)
Indication; upper limit indicator lamp (red)
— lights up when CO2 concentration
exceeds upper limit.
lower limit indicator lamp (red)
— lights up when CO2 concentration
is below the lower limit.
Indicator:
CO2 concentration actual scale, moving
coil type, JIS 2.5 class
Power supply: 100, 115, 200, 220V AC ± 10%, 50/60Hz
(as specified)
Power consumption:
Approx. 18VA
Ambient temperature:
0 to 40°C
Ambient humidity:
90% RH or less
Storage temperature:
–20 to 50°C
Sample gas temperature:
0 to 50°C
Gas sampling: Aspirating pump (with power ON-OFF
switch), membrane filter built in, sample
gas flow rate approx. 0.6r/min
Performance specifications
Repeatability: ± 1% FS
Zero point drift: Within ± 10%/6 months
Response time: Within 10 seconds (for 90% response)
Warmup time: Approx. 30 minutes
Linearity:
± 3% FS (only for 0 to 0.2% range)
Structure and material
Enclosure:
Indoor dust-proof type
Case material: Case cover (ABS resin), base plate (steel
plate)
Surface color: Case (Munsell 3.1Y7.0/1.1)
Lid (Munsell 9.2YR4/1)
Material of parts contacting gas:
SUS304, corrosion-resistant aluminum
Mounting:
Wall mounting
Outer dimensions (H x W x D):
257 x 220 x 85mm
Mass {Weight}: Approx. 3kg
Piping:
4.8mm dia. hose end (sample gas inlet)
Wiring:
M3 screw terminal
EDS3-104c
Date Apr. 1, 2011