English
Language : 

EDS2-17 Datasheet, PDF (1/8 Pages) Fuji Electric – OPTICAL TEMPERATURE TRANSMITTER
FFI SYSTEM
OPTICAL TEMPERATURE TRANSMITTER
DATA SHEET
FUK···3, FUL···3, FUM···1
The Model FUK 3/FUL 3/FUM 1 is Optical Temperature
Transmitter for thermocouple or platinum resistance bulb
used for measuring the temperature of different fluids. The
transmission unit incorporates a microprocessor that car-
ries out digital processing of signals for ensuring a high ac-
curacy and an intelligent operation.
FUK
A fiber optical cable used for the signal transmission line
FUL
forms an optical field instrumentation system together with
an optical star coupler and a master station.
MODEL TYPE CONFIGURATION
1) Thermocouple temperature transmitter (integrated type),
Model type: FUK
2) Resistance bulb temperature transmitter (integrated type),
Model type: FUL
3) Temperature transmitter (separate type), Model type:
FUM
FUM
FEATURES
1. Resistive to noise and lightning
Optical signal ensures a reliable signal transmission,
because it is not be affected by external noise and in-
ductive lightning. Use of a nonmetallic optical (fiber) cable
prevents propagation of inductive lightning through the
cable, so a signal transmission immune to lightning can
be realized.
2. Reliability due to redundant configuration
Host system can be duplicated by using two optical cable
trunk lines (between an optical star coupler and host
system). This enhances reliability of users' systems.
3. Intrinsic safety type explosion-proof
Each equipment with a built-in battery can be constructed
so as to be an intrinsic safety type individually (intrinsic
safety type barrier unnecessary).
SPECIFICATIONS
Functional specifications
Fluids measured: Liquid, gas or steam
Measuring range, measuring span:
(1) Integrated type (FUK, FUL)
J thermocouple
E thermocouple
K thermocouple
Resistance bulb Pt100
Measuring range
-200 to +400°C
-200 to +400°C
-200 to +400°C
-200 to +400°C
Measuring span
Minimum Maximum
50°C
50°C
50°C
50°C
400°C
400°C
400°C
400°C
(2) Separate type (FUM)
J thermocouple
E thermocouple
K thermocouple
R thermocouple
T thermocouple
Resistance bulb Pt100
Measuring range
-200 to +750°C
-200 to +800°C
-200 to +1200°C
0 to +1600°C
-200 to +350°C
-200 to +600°C
Measuring span
Minimum Maximum
100°C
100°C
150°C
200°C
50°C
80°C
750°C
800°C
1200°C
1600°C
350°C
600°C
Operating pressure:
Flange type ... Rated pressure of flange
Screw-in type ... 4 MPa or less
Output:
Optical digital signal
Burnout:
If sensor is burnt out, last output is held,
and alarm is delivered (detecting unit fail-
ure)
Self-diagnosis: Displayed on indication unit (option) and
transmitted to master station.
Diagnosis item
Measuring range abnormal
Detecting unit failure
Amplifier abnormal
Battery voltage
Battery voltage low alarm
Host system Indication unit
EDS2-17
Date May 20, 2004