PUM Series
Multi-loop module type
Temperature controller
DATA SHEET
Enhanced communication
Module (PROFIBUS) [PUMCP]
PUMCP is a communication module, which connects module
type temperature controller PUM series with PROFIBUS
system. Compatible with PROFIBUS DP-V0, and designed
for high-speed communication at the maximum speed of
12Mbps. Being able to up to 16 units (64 channel) of PUMA
(control module), PUMCP requires minimum wiring, less
space, and saves labor for engineering.
PUMCP
FEATURES
I. Program-less connection to PROFIBUS
1. PROFIBUS DP-V0 compatible
High-speed communication at max.12Mbps
2. Access to all parameters of control module (PUMA/
PUMB) via PROFIBUS
3. High-speed data communication with connected control
modules (PUMA/PUMB)
- Quick data importing and setting data reflection
II. User-friendly structure and functions
1. Lateral connection : Max.16 units (64 channels) + event
input/output module 16 units = total 32 units
Simple wiring for power supply and communication
2. Detachable structure: Terminal block, main unit, and
the base part
→ Easy wiring with detachable terminal blcok
→ Main units exchangeable without re-wiring
SYSTEM SPECIFICATION
1. Product type: Multi-loop module type temperature
controller
2. Module type
1) Analog module: Total maximum 16 units
a) Control module (4 loop/unit)
b) Extended input/output module
- Analog input/output module
(Input/output 4 points/unit)
- Analog input module (Input 4 points/unit)
- Analog output module (output 4 points/unit)
2) Extended input/output (digital) module:
Maximum 16 units
- Event input/output module
(Input/output ; 8 points/unit)
3) Enhanced communication module: 1 unit
3. Connecting method:
Lateral connecting with connectors
- For power supply and RS-485 communication,
any one of connected modules is required to be
connected.
4. No. of loop, input/output
1) Control loop: Max. 64
2) No.of input / output: DI 128 points / DO 128 points
Enhanced communication module
(PROFIBUS) specification
1. General specification
(1) Power supply: 24V DC ±10%
(2) Power consumption: Max. 3.2 W (135 mA)
[when 24V DC is applied]
(3) Insulation resistance: 20MW or more (500V DC)
(4) Withstand voltage:
Power supply ↔ loader communication
1000V AC 1 min.
Power supply ↔ SLD/FG terminal, PROFI-
BUS communication 1000V AC 1 min.
(5) Applied standards:
UL, C-UL, CE Marking, RoHS directive
[Pending for UL and C-UL]
2. PROFIBUS communication module
2.1 PROFIBUS communication
(1) Compliant version: PROFIBUS DP-V0 (Cyclic com-
munication)
(2) Station type: Slave device
(3) Communication speed and distance
Speed
9.6,19.2,
93.75
kbps
187.5
kbps
500 kbps 1.5Mbps
3M,6M,
12Mbps
Distance 1200m
or less
100m
or less
400m
or less
200m
or less
100m
or less
(4) Station number: Settable station number 1 to 99
(5) Communication data length (Cyclic communication)
Remote
input/output
bits
Remote
input/output
words
64 bits
8 words
128 bits
16 words
256 bits
32 words
512 bits
64 words
864 bits
108 words
(6) Connecting cable: Type A compatible cable for PROFIBUS
(7) Connecting method: M3 screw terminal block
(8)Termination resistace: External (220W, 1/2W) or depends
on the internal SW setting.
EDS11-172a
Date Apr. 1, 2011