English
Language : 

EDS11-166A Datasheet, PDF (1/4 Pages) Fuji Electric – PUM Series Multi-loop module type Temperature controller Enhanced communication Module (CC-Link) [PUMCL]
PUM Series
Multi-loop module type
Temperature controller
DATA SHEET
Enhanced communication
Module (CC-Link) [PUMCL]
PUMCL is a communication module, which connects module
type temperature controller PUM series with CC-Link sys-
tem. Compatible with CC-Link Ver1.1 and 2.0, and designed
for high-speed communication at the maximum speed of
10Mbps. Being able to up to 16 units (64 channel) of PUMA
(control module), PUMCL requires minimum wiring, less
space, and saves labor for engineering.
PUMCL
FEATURES
I. Program-less connection to CC-Link
1. CC-Link Ver1.1 / Ver2.0 compatible
High-speed communication at max.10Mbps
2. Access to all parameters of control module (PUMA/
PUMB) via CC-Link
3. High-speed data communication with connected control
modules (PUMA/PUMB)
- Quick data importing and setting data reflection
II. User-friendly structure and functions
1. Lateral connection : Max.16 units (64 channels) + event
input/output module 16 units = total 32 units
Simple wiring for power supply and communication
2. Detachable structure: Terminal block, main unit, and
the base part
→ Easy wiring with detachable terminal blcok
→ Main units exchangeable without re-wiring
SYSTEM SPECIFICATION
1. Product type: Multi-loop module type temperature
controller
2. Module type
1) Analog module: Total maximum 16 units
a) Control module (4 loop/unit)
b) Extended input/output module
- Analog input/output module
(Input/output 4 points/unit)
- Analog input module (Input 4 points/unit)
- Analog output module (output 4 points/unit)
2) Extended input/output (digital) module:
Maximum 16 units
- Event input/output module
(Input/output ; 8 points/unit)
3) Enhanced communication module: 1 unit
3. Connecting method:
Lateral connecting with connectors
- For power supply and RS-485 communication,
any one of connected modules is required to be
connected.
4. No. of loop, input/output
1) Control loop: Max. 64
2) No.of input / output: DI 128 points / DO 128 points
Enhanced communication module
(CC-Link) specification
1. General specification
(1) Power supply: 24V DC ±10%
(2) Power consumption: Max. 3.2 W (135 mA)
[when 24V DC is applied]
(3) Insulation resistance: 20MW or more (500V DC)
(4) Withstand voltage:
Power supply ↔ loader communication
1000V AC 1 min.
Power supply ↔ SLD/FG terminal, CC-Link
communication
500V AC 1 min.
SLD/FG terminal ↔ CC-Link communica-
tion
50V AC 1 min.
(5) Applied standards:
UL, C-UL, RoHS directive
[Pending for UL and C-UL]
2. CC-Link communication module
2.1 CC-Link communication
(1) Compliant version: CC-Link Ver.2.00 / 1.10
(2) Station type: Remote device
(3) Communication speed and distance
Speed 156kbps 625kbps 2.5Mbps 5Mbps
Distance 1200m 900m 400m 200m
or less or less or less or less
10Mbps
100m
or less
(4) Occupation No. of channel/station:
4 stations/station No.setting; 1 to 61
(5) Commnication data length
No.of occupied sta-
tions/extended cyclic
Remote
input/output
(RX/RY)
Remote
registor
(RWr/RWw)
Control module
(PUMA/B) No.
of connectable
units
4 stations occupied × 1
128 bit 16 words
2 or 4 units
4 stations occupied × 2
256 bit 32 words
4 or 8 units
4 stations occupied × 4
512 bit 64 words 8 or 16 units
(6) Connecting cable: Ver1.10 compatible cable for CC-Link
(7) Connecting method: M3 screw terminal block
(8) Termination resistace: External (110W, 1/2W)
EDS11-166a
Date Apr. 1, 2011