This product is an on/off temperature alarm unit which in-
puts signals from a thermocouple or thermistor sensor and
transmits a relay contact output when an input signal reaches
the preset alarm level. This thermostat is most suited for
overheat detection in machines, equipments, etc.
FEATURES
1. Highly compact
Front panel having a DIN size of 24 x 48 mm, as lightweight
as 100 g and besides, depth just 85 mm, featuring a space
saving design.
2. A variety of temperature sensors connectable
Because thermocouples (5 types) and thermistors (0 to
100°C) are connectable, measurement within a wide tem-
perature range from low to high can be covered so as to
match your equipment.
3. Measured and Alarm Temperatures Displayable
Alarm set value and measured temperature value can be
checked promptly using the front keys.
PAS3
4. Alarm point settable in 1°C steps
Temperature can be set in 1°C steps by key operation from
the front.
5. Washable front structure
The front display and operating section has an IP66 water-
proof structure (corresponding to NEMA-4X). This design
allows washing from the panel front.
6. 2 relay contact outputs available
This thermostat is capable of issuing 2 relay contact out-
puts. Therefore, any output of high/low limit pair, 2 upper
limits and 2 lower limits can be selected.
SPECIFICATIONS
Item
Specification
Input Number of inputs: 1
Input signal and measurable range: Refer to Table 1.
Allowable signal source resistance:
Thermocouple input 100 Ω max.
Measurement cycle: 2 sec. or less
Burnout function: Thermocouple input; UUU display
Thermistor input: LLL display
(Upscale or downscale at burnout settable)
Input impedance: Thermocouple input 1 MΩ or higher
Input filter: 0 to 90 sec. (settable in 1 sec. steps)
Primary lag filter
Input value compensation:
Settable within ±10% of measurable range
Indication Indication means: LCD (without back light)
Value/parameter indication: 4 digits of 7 segments each
(However, at the 1st digit, only - or 1 is indicated within -999
to 1999.)
Contents of indication: Measured value, alarm set value 1,
alarm set value 2, various parameters
Each indicator of alarms 1 and 2, ˚C scale
Operation Number of keys: 3 keys, sheet type keys (embossed)
Alarm value setting resolution: 1˚C
Key lock function: (Change of setting can be inhibited.)
Accuracy Indication accuracy: Refer to Table 1.
(However, error of a temperature sensor is not included.)
Reference contact compensation error: ±3˚C (at 23˚C)
Alarm Number of outputs: 1 or 2 (as specified in CODE SYMBOLS)
output Contact structure: 1a contact
Alarm type: Refer to Table 2.
Contact capacity: 220 V AC/30 V DC, 2 A (resistance load)
220 AC/30 DC, 1 A (inductive load)
Mechanical life of contact:
20 million activations or more (100 activations/min.)
Electrical life of contact:
100,000 activations or more (rated load)
Output resetting cycle: 2 sec. or less
Alarm value settable range:
Settable within 0 to 100% of measurable range
Hysteresis width settable range:
0 to 110% of measurable range (settable in 1˚C steps)
Alarm action delay time: Settable within 1 to 120 sec.
Item
Specification
Power
supply
Power supply voltage: 100 V (–15%) to 240 V (+10%) AC
50/60 Hz (±10%)
Power consumption:
3 VA max. (with 100 V AC), 6 VA max. (with 240 V AC)
Operating Ambient temperature: 0 to 50˚C
conditions Ambient humidity: 90% RH max. (condensation unallowable)
Body
Mounting method: Panel flush mounting
Use of optional DIN rail-mounting adapter
allows the instrument to be rail mounted
or wall mounted.
structure External dimensions (H x W x D): 24 x 48 x 85 mm
Weight: Approx. 100 g
Casing material:
Plastic (corresponding to flame resistance grade UL94V-0)
Front protective structure:
IP66 (corresponding to NEMA-4X) when using
Fuji’s genuine front waterproof packing part
External terminals: Plug-in type (for bar terminals)
Finish color: Ivory
Table 1 Input signal, measurable range and indication
acurasy
Input signal
Measurable Minimum
range (˚C)
resolution
Indication
accuracy
Thermocouple J
0 to 800
1˚C
K
0 to 1200
1˚C
R
0 to 1600
4˚C
T
0 to 400
1˚C
E
0 to 600
1˚C
Thermistor PB-36 0 to 100
1˚C
±3˚C
±3˚C
±4˚C
±3˚C
±3˚C
±4˚C
Note 1) Correct indication is not ensured within a range from 0 to 500˚C for
an R type thermocouple.
Note 2) Switching between a thermistor and a thermocouple is not allowed.
Thermocouple input type can be changed by front key operation.