EDS11-139A Datasheet, PDF (1/6 Pages) Fuji Electric – REPLACE CASE | |||
|
REPLACE CASE
DATA SHEET
This replacing case is used in a situation where compact
controller E series and F series are replaced with compact
controller M series.
This product is convenient when wiring from the duct is dif-
ficult. It results in substantial labor savings.
SPECIFICATIONS
1.Types of Compact Controller M series models that
may be built-in
Continuous output type controller,
Model : PDA211Aɹ12 -B
YY
DM
Step output type controller,
Model : PDC211A2-B
Y
Y
M
Continuous output type manual loader,
Model
:
PDB111A2-BA
Y
D
Y
M
Continuous output type setter,
Model : PDF111A2-BRY
Y
M
Continuous output type ratio setter,
Model
:
PDG111Aɹ12 -BRY
Y
M
Electronic indicator,
Model : PDJ111A2-BYY
Y
M
2. Number of input/output points
The specification such as the influence of the accuracy
and environment corresponds to the specification for
Compact Controller M series.
2-1 Analog inputs
⢠Points
: MAX. 7 points
⢠Kind of input : Voltage input
⢠Input range : 1 to 5V DC
Note: The opening input of an step output type controller is
applicable to voltage input specification only.
2-2 Analog outputs
1) Control output or manipulated output
⢠Points
: 1 point
⢠Output signal : 4 to 20mA DC
Note: This function is valid only with a continuous output
type controller or a continuous output type manual
loader.
2) Auxiliary analog output
⢠Points
: 5 points
⢠Output signal : 1 to 5V DC
2-3 Digital inputs /outputs
1) Auxiliary digital input signals
⢠Points
:9 points
PDZE
2) Control output signal (pulse width output âPOâ)
⢠Points
:1 set (2 points)
Note: This function is valid only with an step output type
controller.
Important: Externally cross-connect the control outputs to
prevent the increasing pulse and the decreasing
pulse from being turned on at the same time.
3) Fault output signal (âFLTâ)
⢠Points
:1 point
4) Auxiliary digital output signal
⢠Points
:10 points (with a continuous output type
instrument or an electronic
type indicator)
8 points (with an step output type
controller)
3. Operation ambient specifications
⢠Dielectric strength
: 500V AC Ã 1 minute (Between power
terminals VP, PC and ground terminal)
500V AC Ã 1 minute (Between signal
terminals and ground terminal)
⢠Insulation resistance
: 500V DC, 50M⦠or more
⢠Grounding : D-class grounding
⢠insuration location
: at room
⢠Ambient temperature
: 0 to 50ËC (but, 40ËC or less when multi-
row/-tier mounting)
⢠Temperature change ratio
: 10ËC/H or less
⢠Ambient humidity
: 5 to 90%RH (not condensed)
⢠Continuous vibration
: Not specified. Provide a support in the
panel, which should be fixed to the
case for vibration resistance.
⢠Altiude
: 2000m or lower above the sea level
EDS11-139a
Date Jan. 8, 2008
|
▷ |