English
Language : 

EDS11-124D Datasheet, PDF (1/6 Pages) Fuji Electric – PROGRAM CONTROLLER X (96mm)
PROGRAM CONTROLLER X (96mm)
DATA SHEET
The program controller X (PVX) is a high performance control-
ler designed on the basis of many years of Fuji’s successful
experience and advanced technologies.
PVX
FEATURES
1. Display of 3 different datas
Three different datas such as measured value (PV), set
value (SV) and time can be monitored simultaneously.
2. 20-segment program patterns (9 patterns)
Program patterns can be linked in series or repeated.
3. Full multi-input type
The program controller accepts a large number of inputs
(full multi-input). Up to 11 kinds of thermocouples, 1 resis-
tance bulb, 6 different voltage inputs and a current input
can be connected.
4. Wide input/output functions (option)
The program controller is able to expand the input/output
functions up to 8 points of digital inputs, 11 points of digi-
tal outputs and 2 points of auxiliary analog outputs.
SPECIFICATIONS
Panel size:
96 × 96mm
Input:
Full multi-input
• Thermocouple: J, K, R, B, T, E, S, N, U,
WRe5-26, PL-II
• Platinum resistance bulb: Pt100
• DC voltage/current
Input accuracy: ±0.2% of full scale, ±1 digit
Input sampling cycle: 100ms
Control action: PID with auto-tuning
Control output: • Relay contact
• Voltage pulse output (for SSR drive)
• Current output
Alarm output: 2 points (ALM1, ALM2)
Program function: • Number of patterns: 9 patterns (max.)
• Number of segments/patterns: 20 seg-
ments
• Multi-memory (PID, etc.): 9 sets
• Pattern linkage/repeat function: pos-
sible
• Time setting: hour/minute or minute/
second
Operation mode: • Program operation
• Fixed value (FIX) operation
• Manual (MAN) operation
Digital input/output:
• Time signal output: 4 points (TS1, TS2,
TS3, TS4)
• External command input: 4 points (Re-
set, Run, Hold, Advance)
• Pattern select input: BCD 1 digit (23, 22,
21, 20)
• Status output (Output informations): 3
points (Reset, Run/Hold, End)
Option:
• Auxiliary analog output: 2 points (AO1,
AO2)
• Expansion digital output: 2 points (TS5,
TS6 or ALM3, ALM4)
Power source: Flexible supply voltage: 100 to 240V AC
EDS11-124d
Date Jan. 31, 1997