English
Language : 

EDS11-118C Datasheet, PDF (1/10 Pages) Fuji Electric – FC SERIES COMPACT CONTROLLER™–Super (CC-S)(BASIC PID AND FREELY CONFIGURABLE, STEP OUTPUT TYPE)
FC SERIES COMPACT CONTROLLER™–Super (CC-S)
(BASIC PID AND FREELY CONFIGURABLE, STEP OUTPUT TYPE)
DATA SHEET
PNC3
The Compact Controller-S (Basic PID and freely con-
figurable type) is a compact single-loop controller using a
microprocessor. It receives proportional signals from e.g.
thermocouples and RTD's etc., as input, and is equipped
with abundant control and computation functions to allow
configuring a flexible system with a high cost/performance,
above all, as stated below:
— FIELD CONFIGURABLE SLC
— AUTO TUNING FUNCTIONS
— RS-422 DATA LINKAGE
as standard.
FEATURES
1) Versatile functions
• All closed loop control functions, such as cascade, ratio,
time scheduling, Iogic control, etc. are performed in one
controller.
• 86 kinds of control functional blocks (Wafers).
• Generic interface RS-422 availability for personal com-
puter (e.g., IBM PC-AT) for supervision, operation, mainte-
nance, configuration, etc.
• Auto tuning capability.
• Pass code security.
2) Simple and flexible
• Basic PID control configuration can be programmed in
less than 1 (one) minute from front panel.
• No program loaders and accessories necessary.
• No software programming knowledge necessary.
• Application oriented control function is configurable by
connecting the functional blocks.
• Field Configurable through front panel.
• Front panel operation
Operations such as parameter setting, auto/manual
changeover, etc. are all achieved from the front panel.
3) Highly reliable
• Highly reliable with MTBF of 200,000 Hr per MIL Standard
217D.
• LED's are used for bargraph and parameter indication.
• Nonvolatile memory enables to retain parameters in case
of power failure.
4) Update hardware technology
• Custom LSI.
• Surface Mounting Technology.
SPECIFICATIONS
1. Control system configuration
There are two methods of control system configuration
for CC-S, one is configuration by Basic PID and the other
is by wafer connection.
Various types of configuration examples are shown
"VARIOUS CONTROL EXAMPLES" stated hereafter.
(1) Configuration by basic PID (fixed configuration)
Basic PID control function is fixedly defined as stand-
ard control function in the controller beforehand.
Configuration of basic PID can be performed through
simple operation on the front panel keys, where wafer
connection mentioned below is unnecessary.
Computation wafers such as square root, filter, Iimiter,
non linear, etc. can be made valid or invalid by simple
operation of front panel keys.
EDS11-118c
Date Jan. 27, 1999