English
Language : 

EDS11-115G Datasheet, PDF (1/6 Pages) Fuji Electric – FC SERIES SETTER (CONTINUOUS OUTPUT TYPE)
FC SERIES SETTER (CONTINUOUS OUTPUT TYPE)
DATA SHEET
The FC series setter is used for remote setting of a con-
troller or variable constant setting of various types of com-
puting elements.
This instrument uses a solid state indicator and a push-
button operation system to provide reliable monitoring and
operating functions.
PNF3
FEATURES
1. High reliability
This instrument is designed with few mechanical parts.
It is mainly composed of electronic parts such as a solid
state indicator which was formerly consisted of mechani-
cal parts.
2. International standards
This instrument is compact in size, conforming to inter-
national standards IEC. It operates on 24V DC power to
deliver 1 to 5V DC signals as recommended by IEC stand-
ards.
100 and 200V AC power are also available for conven-
ience of operation.
3. Front panel operation
Process values and set points can be read accurately
with digital indications on panel front. Various parameter
settings and setting operations are also possible from
the front panel of the instrument.
FUNCTIONAL DIAGRAM
Process value
input (PV)
Linearize
Square-root
extraction
Filter
PV SV
External set point
input (CAS or PI)
(1 to 5V DC,
pulse width,
or pulse number)
Remote
acknowledge
signal (R-ACK)
Limiter
HL
R
L
FAULT
KPV
ALM
Local mode
output (LS)
Remote request
(R-REQ)
Compensated
process
value signal
(KPV)
Set point
output signal
(SV)
FLT output
High alarm
output (H)
Low alarm
output (L)
EDS11-115g
Date Aug. 15, 1996