English
Language : 

EDS11-106E Datasheet, PDF (1/6 Pages) Fuji Electric – FC SERIES RATIO SETTER
FC SERIES RATIO SETTER
DATA SHEET
The FC series ratio setter is used to set ratio for ratio
control, and its set point signal is transmitted to a controller.
This instrument uses a solid state indicator and a push-
button operation system to provide reliable monitoring and
operating functions.
It also accepts a thermocouple, a resistance bulb and a 4
to 20mA DC input optionally.
PNG1
FEATURES
1. High reliability
This instrument is designed with few mechanical parts.
It is mainly composed of electronic parts such as a solid
state indicator which was formerly consisted of mechani-
cal parts.
2. International standards
This instrument is compact in size, conforming to inter-
national standards IEC. It operates on 24V DC power to
deliver 1 to 5V DC signals as recommended by IEC stand-
ards.
100 and 200V AC power are also available for conven-
ience of operation.
3. Front panel operation
Process values and set points can be read accurately
with digital indications on panel front. Various parameter
settings and setting operations are also possible from
the front panel of the instrument.
FUNCTIONAL DIAGRAM
Process value
input (PV)
Square-root
Linearize extraction Filter
PV
SV
R
B1
SO = R X (SV+B3) X
B2
(PV–B1) + B2
B3
Limiter
HL
External set point
input (CAS or PI)
(1 to 5V DC,
pulse width,
or pulse number)
Remote
acknowledge
signal (R-ACK)
Limiter
R
HL
L
SV
SO2
KPV
SO
ALM
Local mode
output (LS)
Remote reques
(R-REQ)
Compensated
process value
signal (KPV)
Set point
output (SO)
Squared set
point output
(SO2)
Ratio output
signal (SV)
High alarm
output (H)
Low alarm
output (L)
EDS11-106e
Date Jul. 1, 1994