English
Language : 

MPLUS120K Datasheet, PDF (1/1 Pages) FSP TECHNOLOGY INC. – Modular design decreases MTTR
UPS
Mplus 120K
FEATURES
N+1 or N+R Parallel Redundancy for power guarantee
Modular design decreases MTTR
High scalability
Built-in maintenance bypass switch for easy
maintenance without interruptible
High efficiency double conversion online UPS
Adjustable battery numbers
Adjustable charging current
Graphic 5.7'' LC D design for easy configuration
PHASE (ONLY FOR ONLINE UPS)
Phase:
3-phase in / 3-phase out
INPUT
Ca pa c ity :
Vo lta g e :
Voltage Range:
Frequency Range:
120 KW
3 x 400 VAC (3Ph+N)
305-478 VAC (3-phase) @
100% load 190-520 VAC (3-
phase) @ 50% load
40Hz ~ 70 Hz
O U TP U T
AC Voltage Regulation
(Batt. Mode) :
±5 %
Frequency Range
(Batt. Mode):
46~54Hz or 56~64Hz
Wa v e fo r m
(Batt. Mode):
Pure Slin Wave
BATTERY
Battery Type:
Battery Number:
Typical Recharge
Time:
NONE
NONE
NONE
SAFETY STANDARD APPAOVAL
P RO TE C TIO N
Full Protection:
Full Protection
P HYSIC AL
Output Receptacles:
Dimension:
Net Weight (kgs):
India, French, Schuko,
NEMA, and IEC selections
600mm(L) x 1100mm(W) x
2030mm(H)
NONE
OPERATING ENVIRONMENT
Hum idity :
0-90 % RH @ 0- 40°C
(non-condensing)
Noise Level:
NONE
MANAGEMENT
Optional USB/RS-232
Port:
Support Windows
98/2000/2003/XP/Vista/2008,
Windows 7, Linux, and MAC 8
This content is subject to change, please refer to specification for m ore detail.