GX-M Cylindrical Inductive Proximity Sensor
SERIES
PRECAUTIONS FOR PROPER USE
• Never use this product as a sensing device for
personnel protection.
• In case of using sensing devices for personnel
protection, use products which meet laws and
standards, such as OSHA, ANSI or IEC etc.,
for personnel protection applicable in each
region or country.
Mounting
• The tightening torque should be under the value given
below.
Model No.
Sensor size
Tightening torque
Sensor
Connector
(Note)
M8
5 N·m
2 N·m
GX-M□
M12
M18
6 N·m
15 N·m
2 N·m
2 N·m
M30
40 N·m
2 N·m
GX-M(L)8□-U-J
M8
5 N·m
1.5 N·m
Note: Connector is equipped with -Z type or -J type.
Distance from surrounding metal
• As metal around the sensor may affect the sensing
performance, pay attention to the following points.
Influence of surrounding metal
• T he surrounding metal will affect the sensing performance.
Keep the minimum distance specified in the table below.
$
Type
DC 3-wire shielded type
DC 3-wire non-shielded type
DC 2-wire standard type
DC 2-wire long range type
A (mm in)
M8 M12 M18 M30
3
4
10
20
0.12 0.16 0.39 0.79
-
21
36
66
0.83 1.42 2.60
4.5
6
15
30
0.18 0.23 0.59 1.18
8
12
25
45
0.32 0.47 0.98 1.77
Embedding of the sensor in metal
• S ensing range may decrease if the
sensor is completely embedded
in metal. Especially for the non-
shielded type, keep the minimum
distance specified in the right table.
%
Sensor B
C
size (mm in) (mm in)
M12
12
0.47
12
0.47
M18
18
0.71
18
0.71
M30
30
1.18
30
1.18
&
0HWDO
Note: With the non-shielded type, the sensing
range may vary depending on the
position of the nuts.
Mutual interference
• When two or more sensors are installed in parallel or face
to face, keep the minimum separation distance specified
below to avoid mutual interference.
Face to face mounting
Parallel mounting
'
(
Type
D (mm in)
E (mm in)
M8 M12 M18 M30 M8 M12 M18 M30
DC 3-wire
18 24 60 120 3 4 10 20
shielded type 0.71 0.94 2.36 4.72 0.12 0.16 0.39 0.77
DC 3-wire
non-shielded type
-
84 144 264
3.30 5.67 10.39
-
48 72 120
1.89 2.83 4.72
DC 2-wire
18 24 60 120 3 4 10 20
standard type 0.71 0.94 2.36 4.72 0.12 0.16 0.39 0.77
DC 2-wire long 30 50 100 180 5 8 16 30
range type
1.18 1.97 3.93 7.09 0.20 0.32 0.63 1.18
Wiring
• Make sure that the power supply is off while wiring.
• Verify that the supply voltage variation is within the rating.
• If power is supplied from a commercial switching regulator, ensure
that the frame ground (F.G.) terminal of the power supply is
connected to an actual ground.
• Ensure that an isolation transformer is utilized for the DC power
supply. If an autotransformer is utilized, the main body or power
supply may be damaged.
• If the used power supply generates a surge, connect a surge
absorber to the power supply to absorb the surge.
• In case noise generating equipment (switching regulator, inverter
motor, etc.) is used in the vicinity of this product, connect the frame
ground (F.G.) terminal of the equipment to an actual ground.
• Do not run the wires together with high-voltage lines or power lines or put
them in the same raceway. This can cause malfunction due to induction.
• Damage or burnout may result in case of short circuit of load or
miswiring.
• Make a cable length as short as possible to lessen noise pickup.
Others
• Our products have been developed / produced for industrial use
only.
• Avoid using a product where there is excessive vapor, dust or
corrosive gas, or in a place where it could be exposed directly to
water or chemicals.
• Take care that the sensor does not come in direct contact with
water, oil, grease or organic solvents, such as, thinner, etc.
• Do not use in an environment containing infammable or explosive gases.
• Never disassemble or modify the product.