English
Language : 

PSR3 Datasheet, PDF (5/7 Pages) List of Unclassifed Manufacturers – Softstarters
PSR – The compact range
Description
Product description
• Wide rated operational voltage 208–600 V
• Rated control supply voltage 24 V AC/DC or 100–240 V AC
• Rated operational current 3–105 A
• Wide ambient temperature range, -25 to +60 ºC
• Built-in by-pass on all sizes, saving energy and reducing
installation time
• Potentiometer settings
• Run signal relay on all devices
• TOR signal relay on PSR25 … PSR105
• Optional fieldbus communication using Profibus, Modbus,
Devicenet or CANopen
• DIN rail mounting on PSR3 … PSR45
• Screw mounting on all sizes
• Connection kits for easy connection with ABB’s manual
motor starters
• Sophisticated algorithm eliminating the DC-component and
thereby providing excellent starting performance
The PSR range is the most compact of all ABB’s softstarter
ranges. The compact PSR range makes it possible to fit many
devices into the same enclosure. A PSR together with a MMS
(manual motor starter) makes up a far more compact starting
solution than a Star-Delta starter, for instance.
Flexible mounting
PSR softstarters from 3 to 45 A are possible to mount on a
DIN-rail, ensuring quick and easy mounting. Naturally, all sizes
can be screw mounted.
Few settings
The setup of the PSR is easily done and confirmed using the
three clearly marked potentiometers on the front.
Built-in by-pass for energy saving
The built-in by-pass on all sizes does not only save energy;
it will also ensure the most compact ABB’s softstarter design
and reduce the installation time. Thanks to the reduced heat
generation, the softstarter can be mounted inside high IP class
enclosures.
Suitable for stopping pumps
Even without using torque control, the PSR range is designed
to reduce water hammering. Compared to the direct stops of a
Star-Delta starter or a DOL starter the PSR is superior. See the
stop ramp with step-down voltage below.
System concept with manual motor starters
All PSR softstarter sizes can easily be connected to the
corresponding manual motor starters from ABB by using
the special designed connection kits. This makes both the
mounting and the connection easier and will provide a very
compact starting solution containing short circuit and thermal
protection, isolation function and soft starter - everything that
you need.
Settings
1 Start = 1 ... 20 sec
1
Stop = 0 ... 20 sec - including the step down voltage.
2 Step down = 2% reduction for each second increased stop ramp 2
Stop ramp 10 sec -> step down 80% (20% reduction)
3 Uini = 40 ... 70% results in end voltage = 30 ... 60%
3
3 Uini
1 Start
2 Step down
3 Uend
2 Stop
PSR – The compact range
Overview
PSR3 ... PSR16
Normal start
In-line connected
Softstarter, type
PSR3 PSR6 PSR9
PSR12
(400 V) kW 1.5 3
4
5.5
IEC, max. A 3.9 6.8
9
12
(440-480 V) hp 2
3
5
7.5
UL, max FLA 3.4 6.1
9
11
400 V, 40 ºC
Using manual motor
Manual motor starter (50 kA) type
starters type 1 coordination
will be achieved
MS116
PSR25 ... PSR30 PSR37... PSR45
PSR60 ... PSR105
PSR16 PSR25
7.5
11
16
25
10
15
15.2 24.2
PSR30
15
30
20
28
PSR37
18.5
37
25
34
PSR45
22
45
30
46.2
PSR60 PSR72 PSR85 PSR105
30
37
45
55
60
72
85
105
40
50
60
75
59.4 68
80
104
MS132
MS450
MS495
—
Using gG fuses type
1 coordination will be
achieved
Fuse protection (50 kA) gG Fuse
10 A 16 A 25 A
32 A
Suitable switch fuse for the Switch fuse, type
above gG fuses
OS32GD
Overload protection is used Thermal overload relay
to protect the motor from
over heating
TF42
50 A
63 A
100 A
125 A
OS125GD
TF65
200 A
250 A
OS250D
TF96
TF140DU
The line contactor is not Line contactor, type
required for the softstarter
itself but often used to open
AF9
if OL trips
AF12 AF16 AF26
AF30
AF38 AF52 AF65 AF80 AF96 AF116
Using by-pass will reduce
the power loss and allow
more starts per hour
By-pass contacts
Built-in
8 Softstarters | 1SFC132005C0201, rev. M
1SFC132005C0201, rev. M | Softstarters 9