SU8000RT3U Datasheet, PDF (3/8 Pages) List of Unclassifed Manufacturers – SmartOnline 8kVA On-Line Double-Conversion UPS, 6U Rack/Tower, 200-240V NEMA outlets
Nominal Voltage details
Voltage selection via front panel LCD interface
Frequency compatibility
50 / 60 Hz; Supports 50 to 60 Hz and 60 to 50 Hz conversion
Frequency compatibility details
Output frequency matches input nominal on startup; Frequency conversion mode enables conversion of 60Hz to
50Hz or 50Hz to 60Hz (no de-rating)
Output voltage regulation (line mode) +/- 2%
Output voltage regulation (Economy
line mode)
+/- 10%
Output voltage regulation (Battery
mode)
+/- 2%
Built-in UPS output receptacles
4 L6-20R outlet(s); 2 L6-30R outlet(s)
Output circuit breaker
20A double-pole (x2) protects 2 L6-20R outlets each, 30A double-pole (x2) protects 1 L6-30R outlet each
Output AC waveform (AC mode)
Sine wave
Output AC waveform (battery mode) Pure Sine wave
INPUT
Rated input current (at maximum
load)
Nominal Input Voltage(s) Supported
UPS input connection type
UPS input connection description
Recommended Electrical Service
Phase
46A (200V), 44.2A (208V), 41.8A (220V), 40A (230V), 38.3A (240V)
200V AC; 208V AC; 240V AC
Hardwire
3 wire single phase input (L1, L2, G)
50A
Single-Phase
BATTERY
Full load runtime (minutes)
Half load runtime (minutes)
Expandable battery runtime
External battery pack compatibility
DC system voltage (VDC)
Battery recharge rate (included
batteries)
Battery replacement description
5.5 min. (7200w)
13.5 min. (3600w)
Supports extended runtime with optional external battery packs
BP240V10RT3U; BP240V557C-1PH; BP240V787C-1PH; BP240V1037C-1PH; BP240V1407C-1PH
240
Less than 6 hours from 10% to 90%
Hot-swappable, user replaceable external battery packs
VOLTAGE REGULATION
Voltage regulation description
Overvoltage correction
Undervoltage correction
2% output voltage regulation in standard online, double-conversion mode
Corrects overvoltages up to 300V
Corrects undervoltages as low as 100V
LEDS ALARMS & SWITCHES