English
Language : 

PDUMV40 Datasheet, PDF (2/5 Pages) List of Unclassifed Manufacturers – Single-Phase Metered PDU, 3.8kW 20A 120V two independent circuits, 0U vertical mount mount, 32 NEMA
OVERVIEW
PDU Type
Metered
OUTPUT
Output Capacity Details
Frequency compatibility
Output watts
Output nominal voltage
Overload protection
Outlet quantity / type
Outlet Type
3.8kW total, 1.9kW per circuit (120V input); 4.0kW total, 2.0kW per circuit (127V input); 3.2kW total, 1.6kW per
circuit (100V input), 40A maximum total, 20A maximum per circuit (Agency de-rated to 32A continuous total, 16A
continuous per circuit)
50 / 60 Hz
4800
100-127V nominal, single phase
Two 20A breakers
32 NEMA 5-15/20R
NEMA 5-15R, NEMA 5-20R
INPUT
PDU Input Voltage
Maximum Input Amps (A)
Maximum Input Amps (A) Details
PDU Plug Type
Input cord length (ft.)
Input cord length (m)
Phase
100; 120; 127
40
Each circuit supports 20A maximum (Agency de-rated to 16A continuous)
NEMA 5-20P; NEMA L5-20P
10
3.05
Single-Phase
LEDS ALARMS & SWITCHES
Switches
Front panel LEDs
Switchless design
Dual digital current monitoring displays (1 color-coded ammeter for each circuit)
PHYSICAL
Shipping Dimensions (HWD/in)
Shipping Dimensions (HWD/cm)
Shipping weight (lbs)
Shipping weight (kg)
Unit Dimensions (HWD/in)
Unit Dimensions (HWD/cm)
Unit weight (lbs)
Unit weight (kg)
5 x 71.50 x 2.25
12.7 x 181.61 x 5.72
9.2
4.17
3 x 71.25 x 1.5
7.62 x 180.98 x 3.81
8.2
3.72
2/4