PDUB15 Datasheet, PDF (2/5 Pages) List of Unclassifed Manufacturers – Single-Phase Hot-Swap PDU, 1.4kW 15A 120V, 2U Horizontal Rackmount, 8 NEMA 5-15R outlets, set of 2 NEMA 5-15P input plugs
Once the new UPS is up and running with all connections restored, set the switch back to the UPS setting to once again provide fully-conditioned UPS
power to connected equipment
TAA Compliant Version Available - Order Tripp Lite PDUB15TAA
Specifications
OVERVIEW
PDU Type
OUTPUT
Output Watt Capacity (watts)
Output Capacity Details
Frequency compatibility
Output nominal voltage
Outlet quantity / type
Outlet Type
INPUT
PDU Input Voltage
Maximum Input Amps (A)
PDU Plug Type
Input cord length details
Phase
LEDS ALARMS & SWITCHES
Switches
Front panel LEDs
PHYSICAL
Shipping Dimensions (HWD/in)
Shipping Dimensions (HWD/cm)
Shipping weight (lbs)
Shipping weight (kg)
Unit Dimensions (HWD/in)
Unit Dimensions (HWD/cm)
Unit weight (lbs)
Hot-Swap
1440
1.4kW (120V input), 1.5kW (127V input), 1.2kW (100V input); 15A maximum (Agency de-rated to 12A continuous)
50 / 60 Hz
100-127V nominal, single phase
8 NEMA 5-15R outlets support critical connected loads; 1 designated pass-through 5-15R outlet supports UPS
5-15P input plug
NEMA 5-15R
100; 120; 127
12
NEMA 5-15P
Utility input cable (10 ft / 3m) / UPS input cable (6 ft / 1.8m)
Single-Phase
Manual 2 position transfer switch offers fast switching between UPS and Utility operating modes in less than 6
milliseconds
Lighted indicators confirm UPS and Utility switch position and operating mode
9.25 x 20.23 x 6.1
23.5 x 51.4 x 15.5
11
5
3.42 x 17.32 x 3.03
8.7 x 44 x 7.7
7.7
2/4