English
Language : 

FN3258-130-35 Datasheet, PDF (2/4 Pages) List of Unclassifed Manufacturers – Ultra-compact EMC/RFI Filter for Motor Drives Applications 3-Phase Filters FN 3258
2 EMC/EMI Products
Schaffner Group Datasheets 2014
Filter selection table
Filter
FN 3258-7-44
FN 3258-16-44
FN 3258-30-33
FN 3258-42-33
FN 3258-55-34
FN 3258-75-34
FN 3258-100-35
FN 3258-130-35
FN 3258-180-40
Rated current
@ 50 °C (40°C)
[A]
7 (7.7)
16 (17.5)
30 (32.9)
42 (46.0)
55 (60.2)
75 (82.2)
100 (109.5)
130 (142.4)
180 (197.1)
Typical drive
power rating*
[kW]
4
7.5
15
22
30
37
55
75
90
Leakage current**
@ 400 VAC/50 Hz
[mA]
33.0
33.0
33.0
33.0
33.0
33.0
33.0
33.0
33.0
Power loss
@ 25 °C / 50 Hz
[W]
3.8
6.1
11.8
15.7
25.9
32.2
34.5
43.1
58.3
Input/Output
connections
-44
-44
-33
-33
-34
-34
-35
-35
-40
Weight
[kg]
0.5
0.8
1.2
1.4
2.0
2.7
4.3
4.5
6.0
FN 3258H-7-44
7 (7.7)
4
FN 3258H-16-44
16 (17.5)
7.5
FN 3258H-30-33
30 (32.9)
18.5
FN 3258H-42-33
42 (46.0)
22
FN 3258H-55-34
55 (60.2)
37
FN 3258H-75-34
75 (82.2)
45
FN 3258H-100-35
100 (109.5)
55
FN 3258H-130-35
130 (142.4)
75
FN 3258H-180-40
180 (197.1)
110
33.0
3.8
-44
0.5
33.0
6.1
-44
0.8
33.0
11.8
-33
1.2
33.0
15.7
-33
1.4
33.0
25.9
-34
2.0
33.0
32.2
-34
2.7
33.0
34.5
-35
4.3
33.0
43.1
-35
4.5
33.0
58.3
-40
6.0
* Calculated at rated current, 440 VAC (FN 3258)/480 VAC (FN 3258H) and cos phi = 0.8. The exact value depends upon the efficiency of the drive, the motor and the entire
application.
** Maximum leakage under normal operating conditions. Note: if two phases are interrupted, worst case leakage could reach 5.4 times higher levels.
Typical filter attenuation
Per CISPR 17; A = 50​/50​ sym; B = 50​/50​ asym; C = 0.1​/100​ sym; D = 100​/0.1​ sym
7 to 42 A types
55 to 100 A types
130 and 180 A types