English
Language : 

FN258-7-07 Datasheet, PDF (2/4 Pages) List of Unclassifed Manufacturers – Book-style EMC/RFI Filter for Inverters and Power Drive Systems
2 EMC/EMI Products
Schaffner Group Datasheets 2014
Filter selection table
Filter*
FN 258-7-..
FN 258-16-..
FN 258-30-..
FN 258-42-..
FN 258-55-..
FN 258-75-34
FN 258-100-35
FN 258-130-35
FN 258-180-..
FN 258-250-..
FN 258HV-7-29
FN 258HV-16-29
FN 258HV-30-33
FN 258HV-42-33
FN 258HV-55-34
FN 258HV-75-34
FN 258HV-100-35
FN 258HV-130-35
FN 258HVIT-7-29
FN 258HVIT-16-29
FN 258HVIT-30-33
FN 258HVIT-42-33
FN 258HVIT-55-34
FN 258HVIT-75-34
FN 258HVIT-100-35
FN 258HVIT-130-35
FN 258L-7-..
FN 258L-16-..
FN 258L-30-..
FN 258L-42-..
FN 258L-55-..
FN 258L-75-34
FN 258L-100-35
FN 258L-130-35
FN 258L-180-..
FN 258L-250-07
FN 258P-7-..
FN 258P-16-..
FN 258P-30-..
FN 258P-42-..
FN 258P-55-..
FN 258P-75-34
FN 258P-100-35
FN 258P-130-35
FN 258P-180-..
FN 258P-250-07
Rated current
@ 50 °C (40 °C)
[A]
7 (7.7)
16 (17.5)
30 (33)
42 (46)
55 (60)
75 (82)
100 (110)
130 (143)
180 (197)
250 (275)
7 (7.7)
16 (17.5)
30 (33)
42 (46)
55 (60)
75 (82)
100 (110)
130 (143)
7 (7.7)
16 (17.5)
30 (33)
42 (46)
55 (60)
75 (82)
100 (110)
130 (143)
7 (7.7)
16 (17.5)
30 (33)
42 (46)
55 (60)
75 (82)
100 (110)
130 (143)
180 (197)
250 (275)
7 (7.7)
16 (17.5)
30 (33)
42 (46)
55 (60)
75 (82)
100 (110)
130 (143)
180 (197)
250 (275)
Typical drive
power rating**
[kW]
4
7.5
15
22
30
37
55
75
90
132
5.5
11
22
30
45
55
90
110
5.5
11
22
30
45
55
90
110
4
7.5
15
22
30
37
55
75
90
132
4
7.5
15
22
30
37
55
75
90
132
Leakage current***
@ 440 VAC/50 Hz
[mA]
16.5
18.3
24.2
25.8
25.8
25.8
25.8
30.0
30.0
30.0
13.0
19.0
19.0
21.6
21.6
21.6
21.6
25.0
13.0
19.0
19.0
21.6
21.6
21.6
21.6
25.0
0.8
0.8
0.8
0.7
0.7
0.7
0.7
0.7
0.7
0.7
3.3
3.3
3.3
3.5
3.5
3.5
3.5
3.5
3.5
3.6
Power loss
@ 25 °C/50 Hz
[W]
9
20
21
30
30
24
51
50
73
79
9
20
21
30
30
24
51
50
9
20
21
30
30
24
51
50
9
20
21
30
30
24
51
50
73
79
9
20
21
30
30
24
51
50
73
79
Input
connections
-29
-29
-33
-33
-34
-34
-35
-35
-40
-40
-29
-29
-33
-33
-34
-34
-35
-35
-29
-29
-33
-33
-34
-34
-35
-35
-29
-29
-33
-33
-34
-34
-35
-35
-40
-40
-29
-29
-33
-33
-34
-34
-35
-35
-40
-40
Output
connections
-07
-29
-07
-29
-07
-33
-07
-33
-07
-34
-34
-35
-35
-07
-40
-07
-40
-29
-29
-33
-33
-34
-34
-35
-35
-29
-29
-33
-33
-34
-34
-35
-35
-07
-29
-07
-29
-07
-33
-07
-33
-07
-34
-34
-35
-35
-07
-40
-07
-07
-29
-07
-29
-07
-33
-07
-33
-07
-34
-34
-35
-35
-07
-40
-07
Weight
[kg]
1.0
1.4
1.7
2.5
2.9
3.9
5.5
6.9
11.0
12.0
1.0
1.5
1.8
2.6
3.0
4.3
5.6
7.1
1.0
1.5
1.8
2.6
3.0
4.3
5.6
7.1
1.0
1.4
1.7
2.5
2.9
3.9
5.5
6.9
11.0
12.0
1.0
1.4
1.7
2.5
2.9
3.9
5.5
6.9
11.0
12.0
***To compile a complete part number, please replace the -.. with the required output connection style.
***Calculated at rated current, 440 VAC (FN 258) / 690 VAC (FN 258 HV) and cos phi = 0.8. The exact value depends upon the efficiency of the drive, the motor and the entire
***application.
***Maximum leakage under normal operating conditions (FN 258 at 440 V, FN 258 HV at 690 V). Note: if two phases are interrupted, worst case leakage could reach 5.7 times
***higher levels.