Specifications
Input
Input Voltage
External Fuse
Frequency
Inrush Current
Efficiency
Power factor
Turn-on time
Conducted EMI
Harmonic distortion
Isolation
Leakage current
Hold up time
Warranty
Output
Number of outputs
Normal output voltages
Maximum output current
Auxiliary output
Voltage regulation
Ripple and noise
(20 MHz bandwidth)
Current sharing accuracy
Short circuit protection
Over voltage protection
Thermal protection
Maximum load
Maximum load
Maximum load
Maximum load capacitance
85 – 264 Vac
DC Rating: 120 Vdc – 300 Vdc
(¼” x 1¼”) Cooper Bussmann,
ABC-15,
rated 15 A
Littelfuse,
505 series,
rated 16 A / 500 Vdc
47 ~ 400 Hz
30 A Peak
≥92% @ Full load @ 25°C
ambient 48 V output
(5 x 20 mm) Littelfuse,
216 series,
rated 16 A
(¼” x 1¼”) Littelfuse,
505 series,
rated 16 A / 500 Vdc
≥91% @ Full load @ 25°C
ambient 12 V output
> 0.95 typ. Meets EN61000-3-2
AC on 1.5 sec TYP
EN55022 Class B Information technology equipment — Radio
disturbances characteristics — Limits and methods of measurement
BS EN55022:1998; CISPR 22:1997, incorporating corrigendum
Meets IEC 61000-3-2
Meets IEC 60950
< 3.5 mA @ 264 Vac @ 63 Hz
20 mS typical
2 Years
1 to 4
12 V, 24 V, 36 V and 48 V (contact factory for details)
100 A @ 12 V
[27 A @ 48 V]
5 V @ 0.5 A 50 mV p-p
12 V output (11.3 V ~ 12.5 V)
48 V output (45 V ~ 50 V)
12 V output (197 mV ~ 400 mV p-p) 48 V output (1.6 Vp-p)
5 to 10%
“Fold-Back” Technique
12 V output set point 12.5 V typical 48 V modules 50 V typical
All outputs disabled when internal temperature exceeds safe operating
12 V up to 1200 W
48 V up to 1300 W
5.0 V Aux up to 2.5 W
1000 µF per 12 V output
100 µF per 48 V output
Westcor MicroPAC
Page 2 of 5
Rev 1.0
8/2012
vicorpower.com
800 927.9474