English
Language : 

GT3A-1 Datasheet, PDF (14/24 Pages) List of Unclassifed Manufacturers – Analog Timers
GT3W
Timers
GT3W Series — Dual Time Range Timers
Key features:
• Sequential start, sequential interval, on-delay, recycler,
and interval ON timing functions
• 2 time settings in one timer
• 8 selectable operation modes on each model
• Mountable in sockets or flush panel
• Power and output status indicating LEDs
• Time ranges up to 300 hours
UL, c-UL Listed
File No. E55996
General Specifications
Operation System
Solid state CMOS Circuit
Operation Type
Time Range
Pollution Degree
Over Voltage Category
Multi-Mode
1: 0.1sec to 6 hours, 3: 0.1sec to 300 hours
2 (IE60664-1)
III (IE60664-1)
AF20 100-240V AC(50/60Hz)
Rated Operational Voltage
AD24 24V AC(50/60Hz)/24V DC
D12 12V DC
AF20
Voltage Tolerance
AD24
D12
Disengaging Value of Input Voltage
Range of Ambient Operating Temperature
85-264V AC(50/60Hz)
20.4-26.4V AC(50/60Hz)/21.6-26.4V DC
10.8-13.2V DC
Rated Voltage x10% minimum
-10 to +50ºC (without freezing)
Range of Ambient Storage
and Transport Temperature
-30 to +75ºC (without freezing)
Range of Relative Humidity
Atmospheric Pressure
Reset Time
Repeat Error
Voltage Error
35 to 85%RH (without condensation)
80kPa to 110kPa (Operating), 70kPa to 110kPa (Transport)
60msec maximum
±0.2%, ±10msec*
±0.2%, ±10msec*
Temperature Error
±0.6%, ±10msec*
Setting Error
±10% maximum
Insulation Resistance
Dielectric Strength
Vibration Resistance
Shock Resistance
Degree of Protection
Power Consumption
(Approx.)
100V AC/60Hz
AF20
200V AC/60Hz
AD24 (AC/DC)
100MΩ minimum (500V DC)
Between power and output terminals: 2000V AC, 1 minute
Between contacts of different poles: 2000V AC, 1 minute
Between contacts of the same pole:750V AC, 1 minute
10 to 55Hz amplitude 0.75mm2 hours in each of 3 axes
Operating extremes: 98m/sec2 (approx.10G)
Damage limits: 490m/sec2 (approx. 50G)
3 times in each of 3 axes
IP40 (enclosure), IP20 (socket)(IEC60529)
2.3VA
4.6VA
1.8VA/0.9W
Mounting Position
Free
Dimensions
Weight (Approx.)
40Hx 36W x 70 mm
72g
* For the value of the error against a preset time, whichever the largest applies.
Contact Ratings
Allowable Contact Power
Allowable Voltage
Allowable Current
Maximum permissible
operating frequency
Rated Load
Conditional Short Circuit
Electrical
Life
Mechanical
960VA/120W
250V AC/150V DC
5A
1800 cycles per hour
1/8HP, 240V AC
3A, 240V AC (Resistive)
5A, 120V AC/30V DC
(Resistive)
Fuse 5A, 250V
100,000 op. minimum
(Resistive)
20,000,000 op. minimum
856
www.IDEC.com