LC1D18P7 Datasheet, PDF (103/252 Pages) List of Unclassifed Manufacturers – TeSys™ IEC-Style Contactors and Starters
TeSys™ D-Line Contactors and Starters
Characteristics of Auxiliary Contacts, Timers, and Accessories
Interface Modules for Contactors
Environment
Conforming to standards
Meets the essential requirements
of the LV & EMC directives
IEC 60255-5
Product certifications
UL, CSA
Protective treatment
Conforming to IEC 60068
“TH”
Degree of protection
Conforming to VDE 0106
Protection against direct finger contact IP 2X
Ambient air temperature
around the device
Storage
Operation
Permissible for operation at Uc
°C
- 40 to + 80 (- 104 to + 176 °F)
°C
- 25 to + 55 (- 77 to + 131 °F)
°C
- 25 to + 70 (- 77 to + 158 °F)
Other Characteristics
Module type
LA4DFBQ
With relay
LA4DFB LA4DFE LA4DLB LA4DLE
With relay With relay With relay + override
LA4DWB
Solid state
Rated insulation voltage
Conforming to IEC 60947-1
V
5
250
Rated operational voltage
Conforming to IEC 60947-1
V
415
250
Indication of input state
By integral LED which illuminates when the contactor coil is energized
Control voltage (E1-E2)
V
dc 24
dc 24
dc 48
dc 24
dc 48
dc 24
Permissible variation
V
17 to 30
17 to 30 33 to 60 17 to 30 33 to 60 5 to 30
Input signals
Current consumption at 20 °C (68 °F)
mA
25
State “0” guaranteed for
UV
< 2.4
I
mA
<2
25
< 2.4
<2
15
< 4.8
< 1.3
25
< 2.4
<2
15
< 4.8
< 1.3
8.5 for 5 V
15 for 24 V
< 2.4
<2
State “1” guaranteed for
UV
17
17
33
17
33
5
Built-in protection
Against reverse polarity
Of the input
By diode
By diode
Electrical durability at 220/240 V
In millions of operating cycles
3
10
10
3
3
20
Maximum immunity time to micro-breaks
ms
4
4
4
4
4
1
Power dissipated
At 20 °C (68 °F)
W
0.6
0.6
0.6
0.6
0.6
0.4
With coil:
ac 24 to 250 V
–
LC1D40 to D150
–
Direct mounting without contactor
ac 100 to 250 V
–
–
LC1D40 to D115
ac 380 to 415 V
LC1D40 to D150
–
–
With coil:
Mounting with cabling adaptor LAD-4BB
ac 24 to 250 V
ac 380 to 415 V
–
LC1D09 to D38,
DT20 to DT40
LC1D09 to D38, DT20 to DT60
–
LC1D09 to D38,
DT20 to DT60
–
Total operating time
at Uc (of the contactor)
Operating times depend on the type of contactor electromagnet and its control mode.
The closing time “C” is measured from the moment the coil supply is switched on to initial contact of the main poles. The opening time “O” is
measured from the moment the coil supply is switched off to the moment the main poles separate.
LC1D09 to D38, DT20 to DT60 LC1D40 to D65
LC1D80 and D95
With LA4DF, DL
N.O. ms
N.C. ms
20 to 30
16 to 24
28 to 34
20 to 24
28 to 43
18 to 32
Cabling
Phillips N° 2 and Ø 6 mm
Flexible or solid cable
with or without cable end
mm2
mm2
Min.: 1 x 1 (#12 AWG)
Min.: 2 x 2.5 (#12 AWG)
Catalog Number: page 111
Dimensions: pages 122, 123
Schematics: pages 126, 127