English
Language : 

TRV-300 Datasheet, PDF (1/2 Pages) List of Unclassifed Manufacturers – Switch Mode LED Drivers
300W TRV-300 Series
Switch Mode LED Drivers
Constant Voltage
Aluminum Housing
Electrical Specifications
Input Voltage Range:
100 - 277 Nom. Vac (90 - 305 V Min/Max)
Frequency:
50/60 Hz Nom. (47-63 Hz Min/Max)
Power Factor:
>0.90 @ full load, 100V through 277V
Input Current:
3.30 A @ 100Vac
Inrush Current:
50.0 A @ 230 Vac
Maximum Power:
300W
Line Regulation:
± 1%
Load Regulation:
± 3%
Typical Efficiency
91-94% @ full load
Turn-on Delay:
Protection:
0.25S
Over-Voltage, Over-Current, Over-Temperature (110°C),
and Short Circuit Protection with Auto Recovery
Environmental Specifications
Minimum Starting Temp: -35ºC
Storage Temperature:
-40ºC to +85ºC
Humidity:
10% to 100%
Cooling:
Convection
Sound Rating:
Class A
MTBF:
250,000 Hours @ 25ºC, 80% load, per MIL-HDBK-217F
Lifetime:
100,000 Hours @ 80% load and Tc = 70ºC
New Surge Protection and HI-POT Testing
Metal Lock Sheet
Nut
• Total Power: 300 Watts
• Input Voltage: 100-277 Vac Nom.
• UL Dry & Damp Location Rated
• IP67
• Ultra-high Efficiency
• High Power Factor
• UL8750
Constant Voltage - Product Specifications
Model Number
Output Voltage Output Current
(Vdc ±5%)
Range (mA)
TRV-300S012ST
12
TRV-300S024ST
24
TRV-300S028ST
28
TRV-300S036ST
36
TRV-300S048ST
48
TRV-300S054ST
54
0-22.9
0-12.5
0-10.71
0-8.33
0-6.25
0-5.55
Max. Output
Power (W)
275
300
300
300
300
300
Typical
Efficiency
91.5%
91.0%
91.5%
92.0%
94.0%
94.0%
HI-POT Test
Normal Application
The new design of this LED driver provides 1.4KV surge protection. To properly
HI-POT test this unit, the surge protection must be disconnected. The screw, nut, and
metal lock sheet on the input side of the driver provide for this. To test, first remove
the nut and lock sheet as shown. After testing, secure the nut and lock sheet to
provide line-to-earth protection.
This HI-POT test feature is available on product manufactured after August 15, 2015.
E332160
Note:
LED drivers are designed and intended to operate LED loads only.
Non-LED loading may be outside the specified design limits of our
LED drivers, and therefore cannot be covered by any warranty.
If you desire to use our LED drivers to operate non-LED loads
please contact us to discuss compatibility.
Specifications subject to change without notice.
Rev 8-28-15
Thomas Research Products • 1225 Bowes Rd • Elgin, IL 60123 • T 847-515-3057 • F 847-515-3047 • www.trpssl.com