SU5000RT3UHV Datasheet, PDF (1/7 Pages) Tripp Lite. All Rights Reserved – SmartOnline 200-240V 5kVA 3.5kW On-Line Double-Conversion UPS, Extended Run, SNMP,Webcard, 5U Rack/Tower, DB9 Serial
SmartOnline 5kVA On-Line Double-Conversion
UPS, 5U Rack/Tower, 200-240V NEMA outlets
MODEL NUMBER: SU5000RT3UHV
Highlights
5000VA / 5kVA / 3500 watt
on-line double-conversion 5U
rack/tower UPS
200/208/220/230/240V 50/60Hz
output, high efficiency economy
mode option
Hot-swappable battery modules
RS232 & EPO ports; support for
SNMP/WEB card options
Front panel LEDs with detailed
LCD monitoring and control
screen
Expandable runtime with optional
external battery packs
NEMA L6-30P input (3 wire);
L6-30R & L6-20R outputs
Description
Tripp Lite 5kVA Smart Online RM UPS. 5000VA on-line, double-conversion UPS for server, network and
telecommunications equipment. Maintains battery derived AC output during blackouts with active, full-time power
conditioning. Fault-tolerant auto-bypass prevents unexpected service interruptions during overload or internal
fault conditions. 3U power module and 2U battery pack install in 5 rack spaces. Full-time sine wave output within
2% of selectable 200/208/220/230/240V AC. Corrects brownouts to 156V and overvoltages to 276V. Frequency
regulation locks output power to 50/60Hz (+/-0.2%)/Expandable runtime with optional rackmount external battery
packs. Double-conversion UPS converts raw input from AC to DC, then back to perfect sine wave AC output with
enhanced protection from harmonic distortion, fast electrical impulses and other hard-to-solve power problems
not addressed by other UPS types. Highly efficient operation in optional economy mode setting, saving BTU heat
output and energy costs. Network-grade AC surge and noise suppression. Network management interfaces
include 2 DB9 ports and SNMPWEBCARD slot. Supports simultaneous detailed monitoring of equipment load
Package Includes
SU5000RT3UPM UPS Power
Module
BP240V5RT2U External Battery
Pack
PowerAlert UPS management
software and complete cabling
Mounting hardware to support
each module in 4-post rackmount
enclosures
Warranty information
Instruction manual
levels, self-test data and utility power conditions via all 3 network interfaces. Includes PowerAlert monitoring
software and complete cabling. Emergency Power Off (EPO) interface. Front panel LEDs and LCD readout with scroll controls support visual monitoring of all
major UPS functions. Audible alarm. Self test. 4-post rackmount accessories included; 2-9USTAND and 2POSTRMKITWM accessories available. L6-30P
plug-in connection; built-in L6-30 & L6-20 outlets. Power Distribution Unit (PDU) options supported. Field-replaceable, hot-swappable external battery packs.
Attractive all-black color scheme. $250,000 connected equipment insurance.
Features
True online, double-conversion UPS provides pure, full-time sine wave AC output free of surges, voltage fluctuations and line noise
5000VA/3500 watt output power capacity compatible with 200-240V applications at 50/60 Hz
3U power module and 2U battery pack installs in any 19 inch rack enclosure using only 5 rack spaces
Double conversion UPS actively converts raw input from AC to DC, then back to perfect sine wave AC output with enhanced protection from harmonic
distortion, fast electrical impulses and other hard-to-solve power problems not addressed by other UPS types
Provides perfectly regulated, sine wave output power free of line noise, transient surges and frequency variation for the most efficient operation of critical
servers, networking and telecommunications equipment
Accepts input voltages between 156 and 276, regulating output within 2% of selected 200/208/220/230/240V nominal voltage