English
Language : 

SM170400 Datasheet, PDF (1/2 Pages) List of Unclassifed Manufacturers – Current and Voltage Controls 3-Phase Voltage Sequence Control
Current and Voltage Controls
3-Phase Voltage Sequence Control
Type SM 170
• 3-phase monitoring relay for phase
sequence/phase loss
• Measures when all 3 phases are present and
have the correct phase sequence
• Output: 10 A SPDT relay
• Plug-in type module
• S-housing
• LED-indication for power supply and output ON
• Power supply is the 3-phased measuring voltage
Product Description
Ordering Key
3-phase plug-in monitoring
and phase sequence/phase-
loss relay. Frequently used to
prevent a 3-phase motor from
running on only 2 phases or
to secure the right phase se-
quence when connecting a
load to the mains.
Housing
Function
Output
Type
Power supply
SM 170 400
Type Selection
Plug
Output
Circular
SPDT
Supply: 220 VAC
SM 170 220
Supply: 380 VAC
SM 170 380
Supply: 400 VAC
SM 170 400
Supply: 415 VAC
SM 170 415
Input Specifications
Output Specifications
Input
Pin 5
Pin 6
Pin 7
Pin 11
Phase L1
Phase L2
Phase L3
Neutral (optional connection)
measures on own supply
Supply Specifications
Power supply AC types
Rated operational voltage
Through pins 5, 6, 7 & 11
220
380
400
415
Internal measuring circuit is
connected to pins 5 & 7
Overvoltage cat. III (IEC 60664)
(IEC 60038)
3 x 220 VAC ± 15%, 45 to 65 Hz
3 x 380 VAC ± 15%, 45 to 65 Hz
3 x 400 VAC ± 15%, 45 to 65 Hz
3 x 415 VAC ± 15%, 45 to 65 Hz
Output
Rated insulation voltage
Contact ratings (AgCdO)
Resistive loads
AC 1
DC 1
or
Small inductive loads AC 15
DC 13
Mechanical life
Electrical life
AC 1
Operating frequency
Dielectric strength
Dielectric voltage
Rated impulse withstand volt.
SPDT relay
250 VAC (rms)
(cont./elect.)
µ (micro gap)
10 A/250 VAC (2500 VA)
1 A/250 VDC (250 W)
10 A/25 VDC (250 W)
2.5 A/230 VAC
5 A/24 VDC
≥ 30 x 106 operations
≥ 2.5 x 105 operations
(at max. load)
≤ 7200 operations/h
≥ 2 kVAC (rms) (cont./elect.)
4 kV (1.2/50 µs) (cont./elect.)
(IEC 60664)
Voltage interruption
Dielectric voltage
Rated impulse withstand volt.
Rated operational power
≤ 40 ms
None (supply/elect.)
4 kV (1.2/50 µs) (line/neutral,
line/line), direct connection
to electronics
2.5 VA
Specifications are subject to change without notice