English
Language : 

RM1E60AA50 Datasheet, PDF (1/4 Pages) List of Unclassifed Manufacturers – Solid State Relays Industrial, 1-Phase Analog Switching Type RM1E
Solid State Relays
Industrial, 1-Phase Analog Switching
Type RM1E
• AC Solid State Relay
• Analog switching (phase-angle control) for resistive
and slightly inductive load applications
• 4 - 20mA or 0 -10V control input
• Rated operational current: 25, 50 and 100 AACrms
• Rated operational voltage: Up to 600 VACrms
• Variable intensity LED-indication according to input
current
• Integral snubber network
RM1E..AA
RM1E..V
Product Description
Ordering Key
The analog switching relay
works in accordance with the
phase angle control principle,
i.e., the output switching point
in the AC sine wave depends
on the control input which can
be either 4-20mA or 0-10VDC.
4 mA or 0VDC correspond to
zero output power whilst 20 mA
or 10VDC correspond to full
output power (near linear pow-
er response). The relay switch-
es off every time the output
current crosses zero, and
switches ON in accordance
with the applied control input.
Solid State Relay
Number of Poles
Switching mode
Rated operational voltage
Control input
Rated operational current
RM 1E 60 AA 50
Type Selection
Switching mode
Rated operational
voltage
Rated operational
current
Control input
E: Analog switching
23: 230 VACrms*
40: 400 VACrms
48: 480 VACrms
60: 600 VACrms
* For nominal operational voltage of 110VACrms, use RM1E23...
** RM1E..V.. require an external supply voltage
Selection Guide
25: 25 AACrms
50: 50 AACrms
100: 100 AACrms
AA: 4 - 20 mADC
V: 0-10VDC**
Rated operational Blocking voltage Control input
voltage
Rated operational current
25 A
50 A
100 A
230 VAC
400 VAC
480 VAC
600 VAC
650 Vp
850 Vp
1200 Vp
1400 Vp
General Specifications
4 - 20 mA
0-10 VDC
4 - 20 mA
4 - 20 mA
0-10 VDC
4 - 20 mA
0-10 VDC
RM 1E 23 ...
Operational voltage range
RM1E..AA..
RM1E..V..
90 to 280 VAC
90 to 265 VAC
Blocking voltage
650 Vp
Operational frequency range
45 to 65 Hz
Power factor
> 0.75
Approvals
UL, cUL, CSA*
CE-marking
Yes
* Approvals pending for RM1E..V...
** Heatsink must be connected to ground for 600V types
RM1E23AA25
RM1E23V25
RM1E40AA25
RM1E48AA25
RM1E48V25
RM1E60AA25
RM1E60V25
RM1E23AA50
RM1E23V50
RM1E40AA50
RM1E48AA50
RM1E48V50
RM1E60AA50
RM1E60V50
RM1E23AA100
RM1E23V100
RM1E40AA100
RM1E48AA100
RM1E48V100
RM1E60AA100
RM1E60V100
RM 1E 40 ...
RM 1E 48 ...
RM 1E 60 ...
340 to 460 VAC
-
850 Vp
45 to 65 Hz
> 0.75
UL, cUL, CSA*
Yes
90 to 550 VAC
200 to 550 VAC
1200 Vp
45 to 65 Hz
> 0.75
UL, cUL, CSA*
Yes
410 to 660 VAC
410 to 660 VAC
1400 Vp
45 to 65 Hz
> 0.75
UL, cUL, CSA*
Yes**
1