PUB02CT23 Datasheet, PDF (1/4 Pages) List of Unclassifed Manufacturers – Monitoring Relays Monitoring Relays Types DUB02, PUB02
Monitoring Relays
1-Phase True RMS AC Over/Under Voltage
Types DUB02, PUB02
DUB02
PUB02
• TRMS AC over/under voltage monitoring
relays
• Measuring if power supply is within set limits
• Measure on own power supply
• Measuring ranges: 24, 115, 230 VAC
• Power ON delay 1 or 6 s selectable by DIP-switch
• Separately adjustable upper/lower level on relative scale
• Adjustable delay on alarm or on recovery (0.1 to 30 s)
• Programmable latching or inhibit at set level
• Output: 8 A SPDT relay N.D. or N.E. selectable
• For mounting on DIN-rail in accordance with
DIN/EN 50 022 (DUB02) or plug-in module (PUB02)
• 22.5 mm Euronorm housing (DUB02)
or 36 mm plug-in module (PUB02)
• LED indication for relay, alarm and power supply ON
Product Description
Ordering Key
DUB02 and PUB02 are pre-
cise TRMS AC window volt-
age monitoring relays.
The relays monitor their own
power supply which is select-
able by DIP-switch (24, 115 or
230 VAC).
The advantage of using the
latch function is that the
relay can be kept energized
even after the end of the
alarm condition. Inhibit func-
tion can be used to avoid
relay operation when not
desired (maintenance, transi-
tions).
The LED's indicate the state
of the alarm and the output
relay.
Housing
Function
Type
Item number
Output
Power supply
DUB 02 C T23
Type Selection
Mounting
DIN-rail
Plug-in
Output
SPDT
SPDT
Supply: 24, 115, 230 VAC
DUB 02 C T23
PUB 02 C T23
Input Specifications
Output Specifications
Input
Own power supply DUB02:
PUB02:
Measuring ranges
Selectable by DIP-switch
24 VAC
115 VAC
230 VAC
Contact input
DUB02
PUB02
Disabled
Enabled
Pulse width
Hysteresis
A1, A2 (24, 115, 230 VAC)
2, 10 (24, 115, 230 VAC)
Upper level Lower level
-5% to +20% -20% to +5%
22.8 to 28.8 V 19.2 to 25.2 V
109 to 138 V 92 to 121 V
218 to 275 V 184 to 242 V
Terminals Z1, Z2
Terminals 8, 9
> 10 kΩ
< 500 Ω
> 500 ms
~ 2% of set value - fixed
Output
Rated insulation voltage
SPDT relay
250 VAC
Contact ratings (AgSnO2)
Resistive loads
AC 1
DC 12
Small inductive loads AC 15
DC 13
µ
8 A @ 250 VAC
5 A @ 24 VDC
2.5 A @ 250 VAC
2.5 A @ 24 VDC
Mechanical life
≥ 30 x 106 operations
Electrical life
≥ 105 operations
(at 8 A, 250 V, cos ϕ = 1)
Operating frequency
≤ 7200 operations/h
Dielectric strength
Dielectric voltage
2 kVAC (rms)
Rated impulse withstand volt. 4 kV (1.2/50 µs)
Specifications are subject to change without notice (27.01.04)