PDUMH15AT Datasheet, PDF (1/4 Pages) List of Unclassifed Manufacturers – Single-Phase Auto Transfer Switch / Metered PDU, 1.4kW 15A 120V, 1U Horizontal Rackmount, 8 NEMA
Single-Phase Auto Transfer Switch / Metered PDU,
1.4kW 15A 120V, 1U Horizontal Rackmount, 8 NEMA
5-15R outlets, 2 NEMA 5-15P inputs
MODEL NUMBER: PDUMH15AT
Highlights
Single phase 15A 120V Auto
Transfer Switch / ATS PDU
Enables redundant-power option
for single-corded network devices
Separate primary & secondary
inputs connect to any two
compatible power sources
1U horizontal rackmount; 2
NEMA 5-15P inputs; 8 NEMA
5-15R outlets
Two digit visual current meter;
Upgrade options available
Applications
Ideal means to provide
single-corded network gear a
redundant power option
Package Includes
Description
PDU with attached 5-15P primary
Tripp Lite Metered ATS / Auto Transfer Switch provides a redundant power option for single-corded network
input cord
devices. Dual input cords support separate connection to PRIMARY and SECONDARY power sources. The
Detachable C13 to NEMA 5-15P
ATS will normally maintain continuous output to all outlets as derived from the primary input cable. If the primary
12 ft / 3.6m secondary input cord
power source becomes unstable or fails altogether, the ATS will switch over to the secondary power source until
1U mounting brackets
the primary input is restored and stable. Super-fast switchover between primary and secondary power sources
User manual with warranty
occurs within milliseconds. ATS functionality is supported by any two compatible AC power sources, regardless
information
of phase angle, to support a variety of advanced redundant power networking applications. Enables fault tolerant
hot-swappable UPS protection when used with a single UPS and fully redundant UPS protection when each cord is connected to a separate UPS system. In a
two-UPS environment, the primary input cable must be supported by a full time sine wave UPS with zero transfer time. Tripp Lite SmartOnline series is highly
recommended for use as the primary UPS in a two-UPS application. ATS configurations utilizing separate mains circuits, backup generators and even
separate utility power grid feeds are fully supported. On-board ATS processor constantly evaluates power quality on both input sources to prevent transfer to
the secondary source when unavailable or of lower quality than the primary source. Front input LED's display primary or secondary power availability.
Features
120V 15A Automatic Transfer Switch (ATS) / Metered PDU (Agency de-rated to 12A continuous)
Provides a redundant power option for critical networking equipment with a single input power cord
2 digit display reports output power consumption in amps
1U horizontal rackmount form factor; 14.5 in. / 36.8 cm depth
8 built-in NEMA 5-15R outlets
Set of two 12 ft. / 3.6m NEMA 5-15P input cables support connection to separate PRIMARY and SECONDARY power sources
ATS circuits normally maintain output sourced from the primary input cable; As primary input power fails or becomes unstable, the ATS will switch to
maintain output sourced from the secondary input cable until power on the primary input is restored and stable
ATS configurations enable fault-tolerant, hot-swappable UPS protection when used with a single UPS and fully redundant UPS protection when each cord
is connected to a separate UPS system (in a two-UPS environment, the primary input cable must be supported by an online UPS with zero transfer time
1/3