Product data sheet
Characteristics
NSYCVF560M115PF
ClimaSys forced vent. IP54, 560m3/h, 115V,
with outlet grille and filter G2
Complementary
Absorbed power
[In] rated current
Noise level < at
Bearing type
Height
Width
Depth
Cut-out dimensions
Product weight
Material
Colour
Ambient air temperature for operation
Ambient air temperature for storage
Maximum pressure
Connections - terminals
IP degree of protection
Device composition
Condition of use
Offer Sustainability
Sustainable offer status
RoHS (date code: YYWW)
REACh
Product environmental profile
Product end of life instructions
Jun 16, 2015
Main
Range
Category
Type of filter
Flow rate
[Us] rated supply volt-
age
Input voltage
ClimaSys CV
Fan
Standard
Free flow rate with standard filter : 586 m3/h at 60
Hz
Free flow rate with standard filter : 562 m3/h at 50
Hz
103...122 V
115 V 50/60 Hz
83 W 60 Hz
65 W 50 Hz
0.72 A 60 Hz
0.6 A 50 Hz
59 dB
Ball
External : 336 mm
External : 316 mm
External : 161 mm
291 x 291 mm
3.2 kg
Injected thermoplastic (ASA PC) for outlet grille
Outlet grille : grey RAL 7035
-15...60 °C
-40...70 °C
140 Pa flow rate 0 m³/h
Terminal block
IP54
1 cut-out template
1 outlet grille front
1 filter front of axial motor
2 protective grille on the front and rear surfaces
1 axial motor
Outside temperature must be 5 °C lower than inside temperature
Filter must be cleaned and replaced regularly
Surrounding environment must be relatively clean
Overfrequent filter replacement should be avoided
Flow rates depends on the work point, see ProClima software
Green Premium product
Compliant - since 0940 - Schneider Electric declaration of conformity
Reference not containing SVHC above the threshold
Available Download Product Environmental
Need no specific recycling operations
1