English
Language : 

NSYCVF300M230PF Datasheet, PDF (1/2 Pages) List of Unclassifed Manufacturers – ClimaSys forced vent. IP54, 300m3/h, 230V,with outlet grille and filter G2
Product data sheet
Characteristics
NSYCVF300M230PF
ClimaSys forced vent. IP54, 300m3/h, 230V,
with outlet grille and filter G2
Complementary
Absorbed power
[In] rated current
Noise level < at
Bearing type
Height
Width
Depth
Cut-out dimensions
Product weight
Material
Colour
Ambient air temperature for operation
Ambient air temperature for storage
Maximum pressure
Connections - terminals
IP degree of protection
Device composition
Condition of use
Main
Range
Category
Type of filter
Flow rate
[Us] rated supply volt-
age
Input voltage
ClimaSys CV
Fan
Standard
Free flow rate with standard filter : 350 m3/h at 60
Hz
Free flow rate with standard filter : 300 m3/h at 50
Hz
145...253 V
230 V 50/60 Hz
37 W 60 Hz
36 W 50 Hz
0.17 A 50 Hz
0.16 A 60 Hz
55...56 dB
Ball
External : 268 mm
External : 248 mm
External : 116 mm
223 x 223 mm
1.3 kg
Injected thermoplastic (ASA PC) for outlet grille
Outlet grille : grey RAL 7035
-10...70 °C
-40...70 °C
158 Pa flow rate 0 m³/h
Faston connector
IP54
1 power cord
1 cut-out template
1 outlet grille front
1 filter front of axial motor
2 protective grille on the front and rear surfaces
1 axial motor
Outside temperature must be 5 °C lower than inside temperature
Filter must be cleaned and replaced regularly
Surrounding environment must be relatively clean
Overfrequent filter replacement should be avoided
Flow rates depends on the work point, see ProClima software
Jun 16, 2015
1