English
Language : 

MU25A63 Datasheet, PDF (1/3 Pages) List of Unclassifed Manufacturers – Manual Motor Starter MU
Manual Motor Starter MU
❚ Overload protection
❚ Short circuit protection
❚ Phase differential detection
❚ DIN rail mounting
❚ Test facility
❚ Ambient temperature compensation
❚ Fingertouch protection
❚ Lockable off position
❚ Designed to EN60947-4-1 and EN60947-2
❚ Bus-bar system
❚ Enclosures
Options and ordering codes
Current Range
Amps
0.10 - 0.16
0.16 - 0.25
0.25 - 0.40
0.40 - 0.63
0.63 - 1.00
1.00 - 1.60
1.60 - 2.50
2.50 - 4.00
4.00 - 6.30
6.30 - 10
10 - 16
16 - 20
20 - 25
Magnetic Short
Circuit Trip-Amps
1.92
3.0
4.8
7.6
12.0
19.2
30
48
75.6
120
192
240
300
Product
MU25A 0.16
MU25A 0.25
MU25A 0.40
MU25A 0.63
MU25A 1.00
MU25A 1.60
MU25A 2.50
MU25A 4.00
MU25A 6.30
MU25A 10
MU25A 16
MU25A 20
MU25A 25
Accessories
Auxiliary Contacts
For fitting to the side of the unit
max 1 block each side.
Contacts
Product
1 Make + 1 Break
(internal mount)
1 Break
1 Make + 1 Break
2 Makes
2 Early Makes
MU25A PE11
MU25A PS01
MU25A PS11
MU25A PS20
MU25A PV20
Specification
Rated insulation voltage UI
Rated current Ith open, at 50˚C
Mechanical life
Electrical life – AC3 duty
Switching frequency
Operate time – approximately
Total power loss (warm condition)
Temperature compensation open
Rating auxiliary switch – AC15
Mounting position
Power consumption – undervoltage trip
– shunt trip
Terminal wiring cross section 1 or 2 wires main
aux
Weight
690V AC
25 amps
100,000 ops
100,000 ops
30 ops per hour
7 mS
6-8 W
–20 to +55˚C
400V 2A
Any
2.7VA 1.8W
2.7VA 1.8W
0.75 – 4mm2
0.75 – 2.5mm2
0.25 Kg
Shunt Trip
Trips out the unit as voltage is applied.
Mounting inside the unit.
Voltage
Product
24 AC
MU25A A24
110 AC
MU25A A110
220-240 AC
MU25A A240
380-415 AC
MU25A A400
MU/03/03
www.imopc.com