English
Language : 

IS1800HG Datasheet, PDF (1/4 Pages) List of Unclassifed Manufacturers – Isolation Transformer - Medical Grade line noise reduction and spike suppression
Isolation Transformer - Medical Grade line noise
reduction and spike suppression
MODEL NUMBER: IS1800HG
Highlights
Complete line isolation, noise
filtering and surge suppression;
ideal for sensitive equipment
1800 watts, 6 outlets, 10-ft.
power cord
Hospital-grade plug and
receptacles
Leakage current less than 100
microamps
Compliant with the Federal Trade
Agreements Act (TAA) for GSA
Schedule purchases
Package Includes
IS1800HG Isolation Transformer
NEMA5-15P replacement plug
User manual with warranty
Description
information
Isolator Series UL60601-1 Listed Medical Grade Isolation Transformers offer line isolation, continuous noise
filtering and enhanced common mode surge suppression. An internal low-impedance isolation transformer component offers 100% isolation from the input AC
line. Full UL60601-1 medical-grade listing with hospital-grade plug and outlet receptacles makes Isolator medical-grade transformers ideal for protection of
sensitive electronic equipment in patient-care areas. Faraday shield reduces the cumulative leakage current of the Isolator and connected equipment to levels
less than 100 microamps. Secondary neutral-to-ground bonding virtually eliminates common mode noise, providing an isolated neutral-ground reference for
sensitive equipment, and an inexpensive alternative to dedicated circuits and site electrical upgrades. Removes EMI/RFI noise, utility switching transients and
harmonics generated by other on-site loads and utility or lightning related surge conditions. Active transformer filtering provides continuous common-mode
noise rejection with no wearable parts. Unique ability to reduce surges in the worst of power environments to harmless levels. Reduces 6000V IEEE587 Cat
A&B ring wave and combination wave test surges to only 0.5V common mode. Model IS1800HG includes 6 widely spaced NEMA 5-15R hospital-grade output
receptacles, a 10-ft. power cord, hospital-grade input plug, circuit breaker overload protection, and lighted power switch. Rugged all-metal unit housing; ships
ready for placement in any industrial, medical, office or network environment. PLUG/OUTLETS: Input - NEMA 5-20P Hospital Grade; Output - 6 NEMA 5-20R
Hospital Grade ELECTRICAL: 120V AC, 60Hz, 2.1A (Requires NEMA 5-15R wall receptacle)
Features
The IS1800HG Medical Grade Isolation Transformer offers line isolation and continuous noise filtering
Internal low-impedance isolation transformer with Faraday shield offers 100% isolation from the input AC line
Full UL60601-1 medical-grade listing with hospital-grade plug and outlet receptacles makes Isolator Hospital Grade transformers ideal for the protection of
sensitive electronic equipment in patient-care areas.
Reduces the cumulative leakage current of the Isolator and connected equipment to levels less than 100 microamps. Secondary neutral to ground
bonding eliminates common mode noise, providing an isolated ground reference for sensitive equipment
Serves as an inexpensive alternative to dedicated circuits and site electrical upgrades
Removes EMI/RFI noise, utility switching transients, load-generated harmonics and ground loops
Active transformer filtering offers continuous common-mode noise rejection with no wearable parts; unique ability to reduce surges in the worst of power
environments to harmless levels
Reduces 6000V IEEE587 Cat A&B ring wave and combination wave test surges to only 0.5V common mode
Includes 6 widely spaced NEMA5-20R hospital-grade output receptacles, a 10-ft. power cord, hospital-grade input plug, circuit breaker overload