Summary:
⢠World-wide ac input ranges and safety
standards
⢠Industry standard packages
⢠Commercial UL/CSA TUV/IEC approvedâ
models to UL/CSA 60950; EN/IEC60950-1
⢠Burn-in with cycling; 3-year warranty
⢠Capacitors have highest CV & ripple current
ratings
⢠Medical Approved to UL2601-1/60601-1,
IEC60601-1 and CSA601.1
⢠Medical leakage 10 μA
⢠MTBF 200,000+ hours per MIL-HDBK-217D
(most units)
⢠All electrolytic caps rated at 105°C
⢠Transformer insulation meets Class F (155°C)
⢠Exceed FCC and CISPR22, Class B conducted
emissions
⢠RoHS Compliant models available (G suffix)
⢠marked to LVD
SPECIFICATIONS
Ac Input
100, 120 and 240 Vac: +10%, -13%; 215 Vac: +12%, -11%; 47 to 63Hz. Toler-
ance for 230 Vac operation is +15%, -10%. Derate output current 10% for 50
Hz operation.
Dc Output
See voltage rating chart. Adjustment range ±5% minimum except HA series.
Line Regulation
±0.05% for a 10% change.
Load Regulation
± 0.05% for a 50% load change.
Output Ripple
3 mV +0.05% of output voltage, peak to peak maximum. All â3-terminal regu-
latorâ outputs: 3 mV +0.2% peak to peak maximum.
Transient Response
<50 microseconds for 50% load change.
Short Circuit Protection
Automatic current limit/foldback.
Overvoltage Protection
Built-in on all 5 V models, set at 6.2 V ±0.4 V. Other models use optional over-
voltage protection.
Remote Sensing
Provided on all models; open sense lead protection built-in (except HA & HTAA
series).
Stability
±0.05% for 24 hours after warmup.
Temperature Rating
0 to 50°C full rated, derated linearly to 40% at 70°C.
Temperature Coefficient
±0.01%/°C maximum.
Efficiency
5 V units: 45%; 12 and 15 V units: 55%; 20 and 24 V units: 60%.
Logic Inhibit and Current-Share
F & G models.
Medical Stock and Vibration
Per Mil-Std-810D, Method 514.3, Category 1, Procedure 1.
Per Mil-Std-810D, Method 516.3, Procedure III.
Storage
-40 to +85 °C.
All specifications are typical at nominal input, full load at 25OC unless otherwise stated
|
▷ |