English
Language : 

GS-AQ911 Datasheet, PDF (1/2 Pages) List of Unclassifed Manufacturers – Space air quality transmitter
www.sontay.com
Technical Overview
The GS-AQ911 is wall-mounting air quality transmitter de-
signed for use for the control of fresh air for ventilation pur-
poses. The GS-AQ911 measures the level of contaminant
gases in an air sample, and is sensitive to most heavy
odours, smoke, solvent gases etc., providing an output pro-
portional to the mixed gas concentration. This signal can be
used to control fresh air fans and dampers according to the
ventilation load. Where the primary contaminant load is hu-
man respiration, it is recommended that a Carbon Dioxide
transmitter is used.
Features
•
Low cost air quality measurement
•
Detects particulates such as cigarette smoke
Data Sheet Ref: 90500997
Issue: 5.1
GS-AQ911
Space air quality transmitter
Specification
Sensor reference
Cal. accuracy
Re-calibration
Housing material
Dimensions
Ambient:
Temperature
RH
Power supply
Output
Country of origin
Tin Dioxide film
±5% of reading
2 years
Flame retardant ABS
85mm x 85mm x 27mm
15°C to 30°C
45 to 65% RH
24Vac/dc (±10%) @ 45mA
0-10Vdc
(0v = Lo contamination)
(10Vdc = Hi contamination)
UK
Product Codes
GS-AQ911
Space air quality transmitter
International Tel: +44 1732 861225
UK Sales Tel: 0845 345 7253
Page 1
International Fax: +44 1732 861226
UK Sales Fax: 0845 345 7353
Whilst every effort has been made to ensure the accuracy of this specification, Sontay cannot accept responsibility for damage, injury, loss or
expense resulting from errors or omissions. In the interest of technical improvement, this specification may be altered without notice.