English
Language : 

FN402-6.5-02 Datasheet, PDF (1/6 Pages) List of Unclassifed Manufacturers – ECOsine™ Compact economy line of passive harmonic filters
EMCandPowerQuality>Approvals
Harmonic filters
FN 3416 / FN 3418
ECOsine™ Compact economy
line of passive harmonic filters
I  Help to comply with IEEE-519, table
10-3 (TDD)
I  Help to comply with EN61000-3-12,
table 3 (THD)
I  Support an efficient utilization of elec-
trical system capacity
I  Ideal for motor drives with 6-pulse
rectifier front-end
I  Same filter for both diode and
thyristor (SCR) rectifiers
Approvals
(in preparation)
Technical specifications
Nominal operating voltage:
Operating frequency:
Nominal motor drive input power rating:
Total harmonic current distortion THID*:
Total demand distortion TDD:
Efficiency:
High potential test voltage:
Protection category:
Cooling:
Overload capability:
Ambient temperature range:
Flammability corresponding to:
Design corresponding to:
MTBF @ 45°C/500V (Mil-HB-217F):
SCCR***:
3x 380 to 500 VAC ±10 % (FN 3416)
3x 380 to 480 VAC ±10 % (FN 3418)
50 Hz ± 1 Hz (FN3416)
60 Hz ± 1 Hz (FN3418)
4 to 200 kW (FN3416)
5 to 250 HP (FN3418)
According to EN61000-3-12, table 3 
<10 % @ rated power (with Ldc)
<15 % @ rated power (without Ldc)
According to IEEE-519, table 10–3
>98 % @ nominal line voltage and power
P  E 2500 VAC (2 sec)
IP20
Internal fan cooling, unregulated
1.6x rated current for 1 minute, once per hour
–25 °C to +45 °C fully operational
+45 °C to +55 °C derated operation**
–25 °C to +70 °C transport and storage
UL 94 V-2 or better
UL508, EN61558-2-20, CE (LVD2006 / 95 /  EC)
200 000 hours
100 kA
* System requirements: THVD <2 %, line voltage unbalance <1 %
Note: performance specifications in this datasheet refer to six-pulse diode rectifiers. SCR rectifier front-end will produce different
results, depending upon the firing angle of the thyristors.
** Iderated = Inominal * √(70 °C-Tamb) / 25 °C
*** External UL-rated fuses required.
Typical electrical schematic
θ
θ
Features and benefits
FN3416 (50Hz) and FN3418 (60Hz) models of
Schaffner ECOsine™ filters help to unburden the
the ECOsine™ product family represent the very ­electrical infrastructure from excess loading and
compact “economy line” of load-applied passive heat caused by current harmonics, and therefore
harmonic filters.
support a better utilization of electric system
They are ideal for non-linear three-phase equip- capacity.
ment with B6 rectifier front-end that do not re- Lower harmonics also reduce the risk of system
quire the industry leading performance provided resonances and potential downtime of sensitive
by Schaffner ECOsine™ FN3410/12 filters.
electronic equipment.
The performance, however, is still sufficient to
FN3416/18 filters upgrade standard motor drives
comply with EN61000-3-12 (for THD) or with IEEE- to “low-harmonic drives” quickly and easily.
519, table 10-3 (for TDD).
Typical applications
I  Three-phase power conversion equipment
with front-end six-pulse rectifier (diode or
SCR)
I Motor drives, like those used e.g. in pump
and fan applications
I Battery chargers, incl. DC fast chargers for
e-cars