English
Language : 

EM4-DINAV53 Datasheet, PDF (1/8 Pages) List of Unclassifed Manufacturers – Energy Management Energy Meter with plug-in Output Modules
Energy Management
Energy Meter with plug-in Output Modules
Type EM4-DIN
• Degree of protection (front): IP 40
• Front dimensions: 9 DIN modules
• RS 422/485 Serial port by means of optional module
• Dual pulse output by means of optional module
• Alarm output (kW dmd) by means of optional module
• Digital inputs for the management of the time periods
and of the H2O and GAS meters
• Class 1 (active energy)
• Class 2 (reactive energy)
• Three-phase multi-function energy meter
• Back-lighted LCD display
• 31/2 DGT instantaneous variables read-out
• 8 DGT + 71/2 DGT energy read-out
• Measurements of system and phase variables: W, Wdmd
• Measurements of total energies: kWh, kvarh
• Measurements of partial energies: kWh, kvarh
• Energy measurements according to EN61036 and EN61268
• Energy measurements by time periods (t1-t2-t3-t4)
selectable by input contacts
• Measurements of m3 H2O and m3 GAS by means of input contacts
• TRMS measurements of distorted wave forms
(voltages/currents)
• Two basic models: direct connection 20(90)AAC,
CT 5(10)AAC and VT connection
• Self power supply (available for some models only) or
auxiliary power supply: 24V, 48V, 115V, 230V, 50-60Hz;
18 to 60VDC, 77 to 143VDC
Product description
How to order EM4-DIN AV5 3 X X XX
Three-phase energy meter
with built-in configuration
key-pad; particularly indicat-
ed for the metering and the
management of the energy
in addition to the metering
and the management of the
signals coming from the
water and gas meters.
Housing for DIN-rail or wall-
mounting, IP40 (front) pro-
tection degree.
Completely sealable housing.
In case of direct connection
up to 90A, the measuring
Type selection
input terminals are suitable
for cables with a cross-sec-
tion area from 6 to 35 mm2.
The special design of the
instrument’s housing allows
to add at any time the inter-
face modules, even when
the instrument is already
installed. The following mod-
ules are available:
- for all versions: pulse output;
- only for the versions with
auxiliary power supply:
digital inputs, RS485 serial
port.
Model
Range code
System
Power supply
Slot A
Slot B
Important note:
• The models from AV0 to AV7 can be equipped with any
type of available modules (slot A and B).
• The models AV8 and AV9 can be equipped only with the
“O” and “R” type modules.
• The AV8 and AV9 models can measure all the parameters
even if the three phase system being connected is missing
one phase.
• The AV2 model is suitable only for three-phase unbalanced
system without neutral.
Range Code
Power supply
Slot A (retransmission)
Slot A (retransmission) cont.
Auxiliary Power Supply:
For all versions
X:
AV0: 208VL-L/20(90)AAC [3] A: 24VAC
O:
AV1: 400VL-L/20(90)AAC [1]
-15+10%, 50-60Hz
AV3: 660VL-L/20(90)AAC [2] B: 48VAC
AV4: 208VL-L/5(10)AAC [3]
-15+10%, 50-60Hz
AV5: 400VL-L/5(10)AAC [1] C: 115VAC
AV6: 100VL-L/5(10)AAC [3]
-15+10%, 50-60Hz
AV7: 660VL-L/5(10)AAC [2] D: 230VAC
Self Power Supply:
-15+10%, 50-60Hz
AV2: 220VL-L/20(90)AAC [4] 4: 18 to 60VDC
AV8: 208VL-L/20(90)AAC [1]
AV9: 400VL-L/20(90)AAC [1]
5: 77 to 143VDC
AV2, AV8 and AV9 only
X: Self Power Supply
System
400VL-L
(-20+15%, 50-60Hz)
3 : Three-phase,
208VL-L
D:
unbalanced load with
or without neutral
(-20+15%, 50-60Hz)
220VL-L
(-10+15%, 50-60Hz)
None
AO2900 module
Dual open collector out-
put. Three operating
modes:
• two pulse outputs
(kWh and kvarh);
• one alarm output
(kW dmd) and one
pulse output
(kWh or kvarh)
• one output
remotely controlled
by a serial port
and one pulse
output (kWh or kvarh)
AQ2940 module
Two digital inputs for
the management of
water and gas meters
[1] Un: -20+15% [2] Un: -30+15% [3] Un: -20+20% [4] Un: -10 +15%
Specifications are subject to change without notice EM4-DINDS1003
R: AO2910 module.
One relay output + one
open collector output.
Operation modes like
module AO2900
Slot B (retransmission)
Only with A-B-C-D-4
power supply
XX: None
S0: AR2950 module
RS422/485
serial port
1