English
Language : 

EM24DIN Datasheet, PDF (1/15 Pages) List of Unclassifed Manufacturers – Energy Management Energy Analyzer Type EM24 DIN
Energy Management
Energy Analyzer
Type EM24 DIN
• Application adaptable display and programming procedure
(Easyprog function)
• Easy connections management
• Certified according to MID Directive (option PF only):
see “how to order” below
• Other version available (not certified, option X and P):
see “how to order” on the next page
• Class 1 (kWh) according to EN62053-21
• Class B (kWh) according to EN50470-3
• Class 2 (kvarh) according to EN62053-23
• Accuracy ±0.5 RDG (current/voltage)
• Energy analyzer
• Instantaneous variables readout: 4 DGT
• Energies/gas/water readout: 7+1 DGT
• System variables: VLL, VLN, Admd max, VA, VAdmd, VAdmd max,
W, Wdmd, Wdmd max, var, PF, Hz, Phase-sequence.
• Single phase variables: VLL, VLN, A, VA, W, var, PF
• Energy measurements: total and partial kWh and kvarh or based on
4 different tariffs; single phase measurements
• Gas, cold water, hot water, kWh remote heating measurements
• Hour counter (6+2 DGT)
• TRMS measurements of distorted sine waves (voltages/cur-
rents)
• Self power supply (AV0-AV2-AV9 inputs)
• Auxiliary power supply (AV5-AV6 inputs)
• 3 digital inputs for tariff selection, DMD synch or gas/
water (hot-cold) and remote heating metering (on request)
• 2 digital outputs for pulses or for alarms or as a mix of them
(on request)
• Dimensions: 4-DIN modules
• Protection degree (front): IP50
• RS485 serial output (on request) (MODBUS-RTU), iFIX SCADA
compatibility
• Dupline communication capability (DP option)
Product Description
Three-phase energy analyzer
with built-in configuration joy-
stick and LCD data displaying;
particularly indicated for active
and reactive energy metering
and for cost allocation. Housing
for DIN-rail mounting with IP50
(front) protection degree. Direct
connection up to 65A and by
means of external current and
potential transformers.
Moreover the meter can be pro-
vided with digital outputs that
can be either for pulse propor-
tional to the active and reactive
energy being measured or for
alarm outputs. In alternative the
RS485 communication port and
3 digital inputs or Dupline port
and 3 digital inputs are avail-
able as an option.
MID Certified according to MID Directive,
Annex "B" + Annex "D" or Annex “B” +
Annex “F” for legal metrology relevant to
active electrical energy meters (see Annex MI-003 of
MID). Can be used for fiscal (legal) metrology.
How to order EM24 DIN AV5 3 X O2 PF
Model
Range code
System
Power supply
Inputs/Outputs
Option
Type Selection for MID version
Range codes
System
Inputs/Outputs
Power supply
AV5:
AV2:
AV9:
400VLL AC - 5(10)A
(CT connection)
VLN : 113V to 230VLN
VLL : 230V to 400VLL
I: 10(65)A
400VLL AC - 10(65)A
(direct connection)
3:
3-phase, 4-wire
balanced load
XX: none
X:
O2: dual open collector
type (dual pulse or one
pulse + one alarm or
D:
dual alarm)
IS: 3 digital inputs for tariff
selection or Gas/Water/
Self power supply
(See “Power supply
specifications”)
115/230VAC (50Hz)
remote heating meter-
Options
ing plus RS485 port
DP: Dupline port plus 3 dig- NOTE: please check the
ital inputs for Gas/
availability of the needed
PF: Certified according to MID Directive, Annex "B" + Annex
"D" or Annex “B” + Annex “F” for legal metrology relevant
to active electrical energy meters (see Annex MI-003 of
water/ remote heating
metering
code on the verification path
tables below before order .
MID). Can be used for fiscal (legal) metrology.
Range
System Power suppInlyput/OutpOutption
Range
System Power suppInlyput/OutpuOtption
AV5
3
D
XX
O2
IS
PF
AV2
3
X
DP
AV9
3
X
XX
PF
O2
IS
Specifications are subject to change without notice EM24 DIN DS 051110