EBSSM2310M Datasheet, PDF (1/2 Pages) List of Unclassifed Manufacturers – Timers Interval | |||
|
Timers
Interval
Type EBS
⢠Fail-safe two-wire connection
⢠Low-cost
⢠Multi-voltage: 24-230 VAC
⢠Interval timer
⢠Time range: 0,5 s - 10 m
⢠Knob-adjustable time setting
⢠Output: SCR 10-500 mA (screws) and SCR 10-700mA
(Fast-ON)
⢠For mounting on DIN-rail in accordance with
DIN/EN 50 022
⢠22,5 mm small Euronorm housing
SCREW
FASTON
Product Description
Ordering Key
Small, low cost monofunc-
tion timer with adjustable
time setting. 2-wire connec-
tion for easy and fail-safe
use (see diagram). For
mounting on DIN-rail or
directly on surface by screw.
The timer is used e.g. with
industrial relays or 3-phase
contactors.
Housing
Function
Small E-line
Output
Power supply
Time range
Fast-ON connection
EBS S M23 10S F
Type Selection
Mounting
Output
Time range
Connection
Supply: 24 - 230 VAC
For DIN-rail
or for screw
SCR
SCR
SCR
0.5 - 10 s
0.1 -1 m
1 - 10 m
Screws
Screws
Screws
EBS S M23 10S
EBS S M23 1M
EBS S M23 10M
For DIN-rail
or for screw
SCR
SCR
SCR
0.5 - 10 s
0.1 -1 m
1 - 10 m
Fast-ON
Fast-ON
Fast-ON
EBS S M23 10S F
EBS S M23 1M F
EBS S M23 10M F
Time Specifications
Time ranges
10 s
1m
10 m
Time range accuracy
Repeat accuracy
Time variation
Within rated power supply
and ambient temperature
Reset
Time and output
0.5 - 10 s
0.1 - 1 m
1 - 10 m
Max. setting: actual time
⥠max. set time
min. setting: actual time
⤠min. set time
⤠0.2%
⤠0.1%/V
⤠0.2%/°C
Power supply interruption
⥠200 ms
Output Specifications
Output
Output current
Maximum load current
(screw terminals)
(Fast-ON connection)
Maximum current for 100 ms
(screw terminals)
(Fast-ON connection)
Minimum load current
Leakage current
Voltage drop
SCR
500 mA
700 m
5.5 A
7A
10 m
⤠3.5 mA @ 230 V
typ.: 2 m
⤠8 VAC
typ.: 5 VAC @ 50 mA
Supply Specifications
Power supply
Rated operational voltage
Rated insulation voltage
Overvoltage cat. III (IEC 60664)
(IEC 60038)
24-230 VAC, -10/+15%
None
Specifications are subject to change without notice (20.07.06)