English
Language : 

DTA01C024 Datasheet, PDF (1/3 Pages) List of Unclassifed Manufacturers – Monitoring Relays Motor temperature
Monitoring Relays
Motor temperature
Types DTA01, PTA01, DTA02, PTA02
• Motor temperature monitoring relay
• Measuring ranges: PTC according to EN 44081
• Remote and local alarm reset (DTA02, PTA02)
• Output: 8 A SPDT relay normally energized
• For mounting on DIN-rail in accordance with DIN/EN
50 022 (DTA01, DTA02) or plug-in module (PTA01,
PTA02)
• 22.5 mm Euronorm housing (DTA01, DTA02) or
36 mm plug-in module (PTA01, PTA02)
• LED indication for relay and power supply ON (DTA02,
PTA02)
• Galvanically separated power supply
DTA01, DTA02
PTA01, PTA02
Product Description
Ordering Key
DTA01, DTA02, PTA01 and
PTA02 are precise thermistor
monitoring relays.
They can be used to monitor
the temperature of the coils of
a motor with built-in PTC’s.
The alarm status of the relay
can be reset by either an
external contact or an internal
button (DTA02, PTA02).
The test button allows the
simulation of the fault condi-
tion (DTA02, PTA02).
The red LED indicates the
alarm status.
Housing
Function
Type
Item number
Output
Power supply
DTA 01 C 230
Type Selection
Mounting Output
Supply: 24 VDC
Supply: 24 VAC
Supply: 115 VAC
Supply: 230 VAC
DIN-rail
Plug-in
DIN-rail
Plug-in
SPST
SPDT
SPDT
SPDT
DTA 01 C 724
PTA 01 C 724
DTA 02 C 724
PTA 02 C 724
DTA 01 C 024
PTA 01 C 024
DTA 02 C 024
PTA 02 C 024
DTA 01 C 115
PTA 01 C 115
DTA 02 C 115
PTA 02 C 115
DTA 01 C 230
PTA 01 C 230
DTA 02 C 230
PTA 02 C 230
Input Specifications
Input (PTC) DTA01, DTA02:
PTA01, PTA02:
Measuring ranges
Max cold PTC resistance
Alarm setpoint
Return setpoint
Short-circuit detection
Measurement voltage
Contact input
DTA02
PTA02
Disabled
Enabled
Alarm reset
Terminals T1, T2
Terminals 5, 6
1500 Ω
3100 Ω ± 10%
1650 Ω ± 10%
0 to 10 Ω
≤2.5V (acc. to IEC 60034-11)
Terminals Z1, Z2
Terminals 8, 9
> 10 kΩ
< 500 Ω
> 500 ms
Output Specifications
Output
Rated insulation voltage
SPST or SPDT relay
250 VAC
Contact ratings (AgSnO2)
Resistive loads
AC 1
DC 12
Small inductive loads AC 15
DC 13
µ
8 A @ 250 VAC
5 A @ 24 VDC
2.5 A @ 250 VAC
2.5 A @ 24 VDC
Mechanical life
≥ 30 x 106 operations
Electrical life
≥ 105 operations
(at 8 A, 250 V, cos ϕ = 1)
Operating frequency
≤ 7200 operations/h
Dielectric strength
Dielectric voltage
≥ 2 kVAC (rms)
Rated impulse withstand volt. 4 kV (1.2/50 µs)
Specifications are subject to change without notice (01.12.04)