DPB02CM23 Datasheet, PDF (1/4 Pages) List of Unclassifed Manufacturers – Monitoring Relays True RMS 3-Phase, Phase Sequence/Loss - Asymmetry
Monitoring Relays
True RMS 3-Phase, Phase Sequence/Loss - Asymmetry
Types DPB02, PPB02
DPB02
PPB02
• TRMS 3-phase phase sequence, phase loss and
asymmetry monitoring relays
• Detect when all 3 phases are present and have the
correct sequence
• Detect if asymmetry level is below the set value
• Measure on own power supply
• Selection of measuring range by DIP-switches
• Adjustable asymmetry on relative scale
• Adjustable delay function (0.1 to 30 s)
• Output: 8 A relay SPDT N.E.
• For mounting on DIN-rail in accordance with
DIN/EN 50 022 (DPB02) or plug-in module (PPB02)
• 22.5 mm Euronorm housing (DPB02)
or 36 mm plug-in module (PPB02)
• LED indication for relay, alarm and power supply ON
Product Description
Ordering Key
3-phase or 3-phase+neutral
line voltage monitoring relay
for phase sequence, phase
loss and asymmetry with
built-in time delay function.
Supply ranges from 208 to
480 VAC covered by two
multi voltage relays.
Housing
Function
Type
Item number
Output
Power supply
DPB 02 C M23
Type Selection
Mounting
Output
DIN-rail
Plug-in
SPDT
SPDT
Supply: 208 to 240 VAC Supply: 380 to 415 VAC
DPB 02 C M23
PPB 02 C M23
PPB 02 C M48
Supply: 380 to 480 VAC
DPB 02 C M48
Input Specifications
Output Specifications
Input
L1, L2, L3, N
DPB02: Terminals L1, L2, L3, N
PPB02: Terminals 5, 6, 7, 11
Measure on own supply
Note: Connect the neutral only
if it is intrinsically at the star
centre
Measuring ranges
208 to 240 VAC
177 to 275 ∆VAC
380 to 480 VAC (DPB02CM48) 323 to 550 ∆VAC
380 to 415 VAC (PPB02CM48) 323 to 475 ∆VAC
Ranges
Asymmetry
2 to 22%
of the nominal voltage
Output
Rated insulation voltage
SPDT relay
250 VAC
Contact ratings (AgSnO2)
Resistive loads
AC 1
DC 12
Small inductive loads AC 15
DC 13
µ
8 A @ 250 VAC
5 A @ 24 VDC
2.5 A @ 250 VAC
2.5 A @ 24 VDC
Mechanical life
≥ 30 x 106 operations
Electrical life
≥ 105 operations
(at 8 A, 250 V, cos ϕ = 1)
Operating frequency
≤ 7200 operations/h
Dielectric strength
Dielectric voltage
2 kVAC (rms)
Rated impulse withstand volt. 4 kV (1.2/50 µs)
Note: The input voltage
must not exceed the maxi-
mum rated voltage or drop
below the minumum rated
voltage reported above.
Specifications are subject to change without notice (18.07.06)