English
Language : 

DPA55CM44 Datasheet, PDF (1/3 Pages) List of Unclassifed Manufacturers – Monitoring Relays 3-Phase Voltage selection
Monitoring Relays
3-Phase Voltage selection
Type DPA55
• 3-phase monitoring relay for phase
sequence
• Detects if voltage is at the desired level (± 10% or ±15%)
• Measures own power supply
• Wide power supply range: 208 to 480 VAC (±15%)
• Output: 5 A SPDT relay normally energized
• For mounting on DIN-rail in accordance with
DIN/EN 50 022
• 17.5 mm DIN-rail housing (DIN 43880)
• LED indication for relay and power supply ON
Product Description
3-Phase relay for detection of
incorrect mains voltage. Also
detecting incorrect phase
sequence and phase loss.
This unit allows to stop
incorrect power supply volt-
age when different from the
desired one.
Power supply range from 208
to 480 VAC plus selection of
the different possible nominal
voltages. For mounting on
DIN-rail. Housing 17.5 mm
wide suitable both for back
and front panel mounting.
Ordering Key
Housing
Function
Type
Item number
Output
Power supply
Type Selection
Mounting
Output
DIN-rail
SPDT
Supply: 208 to 480 VAC
DPA 55 C M44
DPA 55 C M44
Input Specifications
Input
L1, L2, L3
Measuring range
Hysteresis
Terminals L1, L2, L3
Measures on own supply
177 to 550 VAC
< 3V
Supply Specifications
Power supply
Overvoltage cat. II
Rated operational voltage
(IEC 60664, IEC 60038)
through terminals: L1, L2, L3 208 to 480 VAC ± 15%,
45 to 65 Hz
Rated operational power
18 VA @ 400 VAC, 50 Hz
Supplied by L1 and L3
Output Specifications
Output
SPDT relay, N.E.
Rated insulation voltage
250 VAC
Contact ratings (AgSnO2)
Resistive loads
AC 1
DC 12
Small inductive loads AC 15
DC 13
µ
5 A @ 250 VAC
5 A @ 24 VDC
2.5 A @ 250 VAC
2.5 A @ 24 VDC
Mechanical life
≥ 30 x 106 operations
Electrical life
≥ 105 operations
(at 8 A, 250 V, cos ϕ = 1)
Operating frequency
≤ 7200 operations/h
Dielectric strength
Dielectric voltage
≥ 2 kVAC (rms)
Rated impulse withstand volt. 4 kV (1.2/50 µs)
Specifications are subject to change without notice (07.09.06)
1