English
Language : 

DMB01CM24 Datasheet, PDF (1/4 Pages) List of Unclassifed Manufacturers – Timers Multifunction
Timers
Multifunction
Types DMB01, PMB01
DMB 01
PMB 01
• Time range 0.1 s to 100 h
• 7 knob selectable functions:
Op - delay on operate
In - interval
Io - interval on trigger open
Id - double interval
Dr - delay on release
R - symmetrical recycler ON first
Rb - symmetrical recycler OFF first
• Knob selection of time range
• Knob-adjustable time setting
• Automatic or manual start
• Repeatability: ≤ 0.2%
• Output: 8 A SPDT or 8 A DPDT relay
• For mounting on DIN-rail in accordance with DIN/EN
50 022 or Plug-in
• 22.5 mm Euronorm or 36 mm Plug-in module housing
• Combined AC and DC power supply
• LED indication for relay status and power supply ON
Product Description
Ordering Key
Multi-voltage timer with 7
knob selectable functions
and 7 knob selectable time
ranges within 0.1s and
100h. For mounting on DIN-
rail (DMB01) or Plug-in
(PMB01).
Housing
Function
Type
Item number
Output
Power supply
DMB 01 C M24
Type Selection
Mounting
Output
DIN-rail
Plug-in
SPDT
DPDT
SPDT
DPDT
Housing
D-Housing
P-Housing
Supply: 24 VDC and 24 to 240 VAC
DMB 01 C M24
PMB 01 C M24
Supply: 24 to 240 VAC/DC
DMB 01 D M24
PMB 01 D M24
Time Specifications
Time ranges
Knob Selectable
Setting accuracy
Repeatability
Time variation
Within rated power supply
Within ambient temperature
Reset
Manual reset of time and/or relay
Pulse duration
Power supply interruption
Automatic start
0.1 to 1 s
1 to 10 s
6 to 60 s
60 to 600 s
0.1 to 1 h
1 to 10 h
10 to 100h
≤ 5%
≤ 0.2%
≤ 0.05%/V
≤ 0.2%/ºC
Close the trigger contact
between pins A1 and Y1
or 2 and 5
≥ 100 ms
≥ 200 ms
Connect pins A1 and Y1
or 2 and 5
Output Specifications
Output
Rated insulation voltage
Contact Ratings (AgSnO2)
Resistive loads
AC 1
DC 12
Small inductive loads AC 15
DC 13
Mechanical life
Electrical life
Operating frequency
Dielectric strength
Dielectric voltage
Rated impulse withstand volt.
SPDT or DPDT relay
250 VAC (rms)
µ
8 A @ 250 VAC
5 A @ 24 VDC
2.5 A @ 250 VAC
2.5 A @ 24 VDC
≥ 30 x 106 operations
≥ 105 operations
(at 8 A, 250 V, cos ϕ = 1)
< 7200 operations/h
2 kVAC (rms)
4 kV (1.2/50 µs)
Specifications are subject to change without notice (15.12.05)