English
Language : 

CVT-DINAV5AD01X Datasheet, PDF (1/2 Pages) List of Unclassifed Manufacturers – Compact Transducer for AC Measurements
Energy Management
Compact Transducer for AC Measurements
Type CVT-DIN AV1/AV4/AV5
• For AC current/voltage measurement
• Field adjustment capability
• For DIN-rail mounting
• Degree of protection: IP 50
Product Description
Ordering Key
Compact transducer for AC ity. The housing is for DIN-rail
current/voltage measurements mounting and ensures a
with field adjustment capabil- degree of protection of IP 50.
Model
Range code
Measurement
Power supply
Setpoints
Rated output
Calibration
Type Selection
CVT-DIN AV5AD01X
Range code
Power supply
Rated output
Calibration
AV1: 100 VAC - 1 AAC
A:
(max. 120 VAC - 1.2 A)
AV4: 100 VAC - 5 AAC
B:
(max. 120 VAC - 6 A)
AV5: 500 VAC - 5 AAC
C:
(max.600 VAC - 6 A)
D:
24 VAC, -15% +10%, 1:
50/60 Hz 1)
48 VAC, -15% +10%, 2:
50/60 Hz 1)
115 VAC, -15% +10%, 3:
50/60 Hz 1)
230 VAC, -15% +10%, 4:
50/60 Hz (standard)
Analogue output
0 to 20 mA (standard)
Analogue output
4 to 20 mADC 1)
Analogue output
0 to 10 VDC 1)
Analogue output
0 to ±1 VDC 1)
X: Standard calibration
Y: Special calibration,
use ”Y” followed by
requested value
1) On request
Input Specifications
Accuracy
(@ 25°C ± 5°C, R.H. ≤ 60%)
Additional errors:
Humidity
Input frequency
Magnetic field
Ripple
Rated input
AV1:
AV4:
AV5:
± 0.5% f.s.,
(0.1 ln/Un to 1 In/Un)
The given accuracy already
includes: frequency, power
supply, output load influences
< 0.3%, 60% to 90% R.H.
< 0.4%, 62 to 400 Hz
< 0.5%, @ 400 A/m
≤ 1% according to IEC
60688-1 and EN 60688-1
AC frequency range
Overload protection
Cont.: Current:
Voltage:
For 1 s: Current:
Voltage:
1 A (1 V internal shunt/1 Ω imp)/
100 VAC (200 kΩ impedance)
5 A (250 mV internal shunt/
0,05 Ω impedance) /
100 VAC (200 kΩ imp.)
5 A (250 mV internal shunt/
0,05 Ω impedance) /
500 VAC (1 MΩ imp.)
48 to 62 Hz
1.2 x rated input
1.2 x rated input
20 x rated input
2 x rated input
Specifications are subject to change without notice