English
Language : 

BM2R Datasheet, PDF (1/4 Pages) List of Unclassifed Manufacturers – Multi-function or mono-function
BM2R
Timers
Syrline
17.5 mm - 2 Relay 8A
›› Multi-function or mono-function
›› Multi-range (12 function)
›› Multi-voltage 12 →240 V AC/DC
›› LED status indicator (relay version)
›› P ossibility of external load connection in parallel to the
control input
›› 3-wire PNP sensor compatible
Specifications
Functions
A - Ac - At - B - C - D - Di -
H - Ht -N - TL - Tt
Delay
0,5 s →10 days
Output
2 changeover
relays
Output relay
Contact arrangement
Maximum switching voltage
Switching current rate (resistive)
Minimum switching contact
Maximum switching power (resistive)
Electrical life
Maximum rate (at max switching power)
Mechanical life
Rated impulse voltage
Dielectric strength between coil / contacts
Dielectric strength between open contacts
Timing
Timing ranges (7 ranges)
Minimum pulse duration typically (relay version)
Maximum reset time by de-energisation typically (relay version)
Repeatability
Repetition accuracy with constant parameters
Drift Temperature
Voltage-dependent drift
Nominal rating
2x8A
Connections
Supply voltage
Screw terminals 12 →240 V ∿/⎓
Code
BM2R08MV1
2 CO (SPDT) (ChangeOver -Simple Pole Double Throw-)
R1: Follow timing function
R2: Follow timing function / Instantaneous
250 VAC/ 8 A resistive / 250 VDC / 0.3 A resistive
NO / NC : 8A 250 V AC / 8 A 30 VDC @ 25°C
NO / NC : 5A 250 V AC / 5 A 30 VDC @ 60°C
10 mA / 5 VDC
2000 VA / 80 W @ 25°C
105 cycles min at 250 VAC/ 8 A resistive
360 cycles /hour
10 x 106 cycles
5 kV (1.2/50µs)
IEC 60664-1: 5 kV /1 min / 1 mA / 50 Hz
2.5 kV /1 min / 1 mA / 50 Hz
0.5→10s, 0.05→1min, 0.5→10min, 0.05→1h, 0.5→10h, 0.05→1day,
0.5→10days
IEC 1812-1: 30 ms
100 ms with load
IEC 1812-1: 120 ms
IEC 1812-1: ≤ ± 0,5 %
IEC 1812-1: ≤ ± 10 %
≤ ± 0.05 % / °C
≤ ± 0.2 % / V