A82-10 Datasheet, PDF (1/3 Pages) List of Unclassifed Manufacturers – Monitoring Relays AC Current Transformer
Monitoring Relays
AC Current Transformer
Types A 82-10, A 82-20
• 5 types of input: 0 - 25 AAC
0 - 50 AAC
0 - 100 AAC
0 - 250 AAC
0 - 500 AAC
• Output: A 82-10: 0 - 20 mADC (source)
A 82-20: 4 - 20 mADC (sink)
• Easy interface to PLC or setpoint relays
Product Description
AC current metering trans-
former for 25, 50, 100, 250 or
500 AAC. Output current from
the transformer is 0-20 mADC
or 4-20 mADC in accordance
with IEC 60381-1. Can be
used with relays DIB01,
PIB01, DIC01, PIC01 or
S183 or directly connected
to a PLC. Power supply ON
is indicated by a green LED
on the side of the housing.
Ordering Key
Type
Output
Input current
A 82-10 50
Type Selection
Input current
25 AAC
50 AAC
100 AAC
250 AAC
500 AAC
25 AAC
50 AAC
100 AAC
250 AAC
500 AAC
Output current
0 - 20 mA
0 - 20 mA
0 - 20 mA
0 - 20 mA
0 - 20 mA
4 - 20 mA
4 - 20 mA
4 - 20 mA
4 - 20 mA
4 - 20 mA
Type no.
A 82-10 25
A 82-10 50
A 82-10 100
A 82-10 250
A 82-10 500
A 82-20 25
A 82-20 50
A 82-20 100
A 82-20 250
A 82-20 500
Input Specifications
A 82-10/20 25
Current range
0 - 25 AAC
Max. current (continuously)
30 AAC
Max. overload current (t = 30 s) 250 AAC
Rated insulation voltage
Input - output
1000 VAC rms
Overvoltage category
IV (IEC 60664)
Dielectric strength
Dielectric voltage
Rated impulse withstand volt.
6 kVAC rms
12 kV
(1.2/50 µs)
A 82-10/20 50
0 - 50 AAC
60 AAC
300 AAC
A 82-10/20 100
0 - 100 AAC
120 AAC
700 AAC
A 82-10/20 250
0 - 250 AAC
300 AAC
1500 AAC
A 82-10/20 500
0 - 500 AAC
600 AAC
3000 AAC
1000 VAC rms
IV (IEC 60664)
1000 VAC rms
IV (IEC 60664)
1000 VAC rms
IV (IEC 60664)
1000 VAC rms
IV (IEC 60664)
6 kVAC rms
12 kV
(1.2/50 µs)
6 kVAC rms
12 kV
(1.2/50 µs)
6 kVAC rms
12 kV
(1.2/50 µs)
6 kVAC rms
12 kV
(1.2/50 µs)
Specifications are subject to change without notice (25.01.06)