9LG0812P4J001 Datasheet, PDF (1/5 Pages) List of Unclassifed Manufacturers – High Air Flow Long Life Fan | |||
|
80 LG type
High Air Flow Long Life Fan
Ë Features
Long Life
The San Ace 80L LG type has an expected life of 180,000 hours
(approximately 20 years), 1.8 times that of our conventional long life
fan,*1 making this fan ideal for equipment that must operate without
maintenance for extended periods.
High Air Flow and High Static Pressure
The maximum air flow of the San Ace 80L LG type is approximately
1.7 times and its maximum static pressure is approximately
3.5 times that of our conventional long life fan.*1
Low Power Consumption
The power consumption of this new fan is approximately 33% lower
than that of our conventional long life fan.*2
*1 Specification of Model No. 9LG0812P4J001. Our conventional long life fan is
80 x 80 x 25 mm âSan Ace 80Lâ, Model No. 109L0812S401.
*2 Specification of Model No. 9LG0812P4H001. When air flow and static pressure
performance is almost identical. Our conventional long life fan is
80 x 80 x 25 mm âSan Ace 80Lâ, Model No. 109L0812H401.
80Ê·80Ê·25mm
Ë Speciï¬cations
Model No.
Rated Voltage
<Vʧ
Operating
Voltage Range
ʦVʧ
PWM
Duty Cycle
ʦ%ʧNote1)
Rated Current
ʦAʧ
Rated Input
ʦWʧ
Rated Speed
ʦmin-1ʧ
Max. Air Flow
ʦm3/minʧʦCFMʧ
Max.
Static Pressure
ʦPaʧ ʦinch H2Oʧ
SPL
ʦdBʢAʣʧ
Operating
Temperature
Expected Life
ʦËʧ
[h]
9LG0812P4J001
100
0.6
7.2
7,400 2.07 73.0 177 0.71
49
20 Note2)
0.06
0.72 1,800 0.50 17.6 10.4 0.04
16
9LG0812P4G001
100
0.30
3.60 5,500 1.54 54.3 98 0.39
43
12 10.8 to13.2
25 Note2)
0.05
0.60 1,400 0.39 13.7 6.3 0.02
14
9LG0812P4H001
9LG0824P4J001
100
25 Note2)
100
20 Note2)
0.12
0.04
0.28
0.05
1.44 3,700 1.03 36.3 44 0.17
0.48 1,100 0.30 10.5 3.9 0.01
6.72 7,400 2.07 73.0 177 0.71
1.20 2,400 0.67 23.6 18.6 0.07
31
13
ʵ10 to ʴ70 180,000
49
22
9LG0824P4G001
100
0.14
3.36 5,500 1.54 54.3 98 0.39
43
24 21.6 to26.4
20 Note2)
0.02
0.48 1,200 0.33 11.6 4.6 0.01
13
9LG0824P4H001
100
0.05
1.2
3,700 1.03 36.3 44 0.17
31
30 Note2)
0.02
0.48 1,100 0.30 10.5 3.9 0.01
13
Note1 : PWM Frequency : 25kHz Fans do not rotate when PWM duty cycle is 0Ë.
Note2 : Minimum startup duty cycle
Ë Common Speciï¬cations
Ë Material ÅÅÅÅÅÅÅÅÅÅÅÅÅÅÅÅÅÅÅÅÅÅÅÅÅÅ Frame : Aluminum, Impeller : Plastics (Flammability: UL94V-1)
Ë Expected Life ÅÅÅÅÅÅÅÅÅÅÅÅÅÅÅÅÅÅÅÅÅ Varies for each model
(L10: Survival rate: 90% at 60Ë, rated voltage, and continuously run in a free air state)
Ë Motor Protection System ÅÅÅÅÅÅÅÅÅÅ Current blocking function and Reverse polarity protection
Ë Dielectric Strength ÅÅÅÅÅÅÅÅÅÅÅÅÅÅÅÅ 50/60 Hz, 500VAC, 1 minute (between lead conductor and frame)
Ë Sound Pressure Level (SPL) ÅÅÅÅÅÅÅÅ Expressed as the value at 1m from air inlet side
Ë Operating Temperature ÅÅÅÅÅÅÅÅÅÅÅÅ Varies for each model (Non-condensing)
Ë Storage Temperature ÅÅÅÅÅÅÅÅÅÅÅÅÅŠʵ30Ë to Ê´70Ë Ê¢Non-CondensingÊ£
Ë Lead Wire ÅÅÅÅÅÅÅÅÅÅÅÅÅÅÅÅÅÅÅÅÅÅÅÅ ËÊ´RedɹËÊBlackɹSensor: Yellow Control: Brown
Ë Mass ÅÅÅÅÅÅÅÅÅÅÅÅÅÅÅÅÅÅÅÅÅÅÅÅÅÅÅÅÅ Approx. 130g
|
▷ |